Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2006 |
Principal Product | Aircraft Components |
NAICS | 339993 - Fastener, Button, Needle, and Pin Manufacturing |
SIC | 3724 - Aircraft Engines And Engine Parts |
Sales | $10,000,000-$50,000,000 |
# of Employees | 125 |
Plant Area (Sq.Ft.) | 55,980 |
Annual Production | 450,000,000 Units |
Production Hrs. Annual | 4,400 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $122,153 | 1,479,149 | kWh | $0.08 |
Electricity Demand | $23,872 | 4,656 | kW-months/year | $5.13 |
Natural Gas | $18,325 | 1,600 | MMBtu | $11.45 |
TOTAL ENERGY COSTS | $168,661 | |||
RECOMMENDED SAVINGS* | $29,090 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $20,713 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Electricity Usage | Electricity Demand | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $7,890 Cost: $19,500 |
$6,508 | 74,800 | $1,397 | 204 | $(-15) | - |
$6,508 74,800 kWh |
$1,397 204 kW-months/year |
$(-15) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $5,301 Cost: - |
$4,364 | 50,160 | $937 | 137 | - | - |
$4,364 50,160 kWh |
$937 137 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,023 Cost: $1,900 |
$3,287 | 37,787 | $740 | 108 | $(-4) | - |
$3,287 37,787 kWh |
$740 108 kW-months/year |
$(-4) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2312 MINIMIZE NON-ESSENTIAL MATERIAL IN HEAT TREATMENT PROCESS |
Savings: $2,800 Cost: - |
$2,800 | 59,444 | - | - | - | - |
$2,800 59,444 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $2,510 Cost: - |
$2,510 | 25,104 | - | - | - | - |
$2,510 25,104 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2515 USE OPTIMUM THICKNESS INSULATION |
Savings: $2,141 Cost: $3,500 |
$1,750 | 47,304 | $391 | 65 | - | - |
$1,750 47,304 kWh |
$391 65 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $1,798 Cost: $8,041 |
$1,545 | 17,765 | $253 | 37 | - | - |
$1,545 17,765 kWh |
$253 37 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $935 Cost: - |
$766 | 8,800 | $169 | 24 | - | - |
$766 8,800 kWh |
$169 24 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7314 REDUCE VENTILATION AIR |
Savings: $750 Cost: - |
$527 | 2,230 | $223 | 46 | - | - |
$527 2,230 kWh |
$223 46 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $477 Cost: $275 |
$381 | 4,379 | $96 | 14 | - | - |
$381 4,379 kWh |
$96 14 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $465 Cost: $53 |
$383 | 4,400 | $82 | 12 | - | - |
$383 4,400 kWh |
$82 12 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $29,090 Cost: $33,269 |
$24,821 | 332,173 | $4,288 | 647 | $(-19) | - | $24,821 332,173 kWh |
$4,288 647 kW-months/year |
$(-19) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $20,713 Cost: $29,769 |
$17,941 | 225,909 | $2,791 | 421 | $(-19) | - | $17,941 225,909 kWh |
$2,791 421 kW-months/year |
$(-19) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Electricity Usage | Electricity Demand | Personnel Changes |