Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2010 |
Principal Product | Sheetmetal fabrication of vent, smoke, and fire damper units |
NAICS | 332322 - Sheet Metal Work Manufacturing |
SIC | 3444 - Sheet Metalwork |
Sales | $10,000,000-$50,000,000 |
# of Employees | 105 |
Plant Area (Sq.Ft.) | 85,000 |
Annual Production | 15,000 Pieces |
Production Hrs. Annual | 2,000 |
Location (State) | KY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $28,029 | 828,140 | kWh | $0.03 |
Electricity Demand | $41,317 | 3,516 | kW-months/year | $11.75 |
Natural Gas | $73,237 | 5,236 | MMBtu | $13.99 |
TOTAL ENERGY COSTS | $147,125 | |||
RECOMMENDED SAVINGS* | $28,669 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $1,592 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $207 Cost: $585 |
$207 | 5,225 | - | - | - | - | - | - |
$207 5,225 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4131 SIZE ELECTRIC MOTORS FOR PEAK OPERATING EFFICIENCY |
Savings: $5,123 Cost: $58,000 |
$5,123 | 129,496 | - | - | - | - | - | - |
$5,123 129,496 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $2,804 Cost: $5,800 |
$2,804 | 70,870 | - | - | - | - | - | - |
$2,804 70,870 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $3,258 Cost: $800 |
$849 | 21,450 | $2,409 | 17 | - | - | - | - |
$849 21,450 kWh |
$2,409 17 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $995 Cost: $500 |
$620 | 15,664 | $1,000 | 7 | - | - | $(-625) | - |
$620 15,664 kWh |
$1,000 7 kW-months/year |
- - MMBtu |
$(-625) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $15,685 Cost: $48,000 |
- | - | - | - | $15,685 | 1,121 | - | - |
- - kWh |
- - kW-months/year |
$15,685 1,121 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7444 CLOSE HOLES AND OPENINGS IN BUILDING SUCH AS BROKEN WINDOWS |
Savings: $597 Cost: $50 |
- | - | - | - | $647 | 46 | $(-50) | - |
- - kWh |
- - kW-months/year |
$647 46 MMBtu |
$(-50) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $28,669 Cost: $113,735 |
$9,603 | 242,705 | $3,409 | 24 | $16,332 | 1,167 | $(-675) | - | $9,603 242,705 kWh |
$3,409 24 kW-months/year |
$16,332 1,167 MMBtu |
$(-675) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $1,592 Cost: $550 |
$620 | 15,664 | $1,000 | 7 | $647 | 46 | $(-675) | - | $620 15,664 kWh |
$1,000 7 kW-months/year |
$647 46 MMBtu |
$(-675) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||