Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2015 |
Principal Product | Pumps |
NAICS | 333911 - Pump and Pumping Equipment Manufacturing |
SIC | 3561 - Pumps And Pumping Equipment |
Sales | $50,000,000-$100,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 190,000 |
Annual Production | 35,500 Pieces |
Production Hrs. Annual | 8,760 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $178,568 | 5,537,350 | kWh | $0.03 |
Electricity Demand | $108,479 | 10,536 | kW-months/year | $10.30 |
Natural Gas | $265,325 | 52,190 | MMBtu | $5.08 |
TOTAL ENERGY COSTS | $861,850 | |||
RECOMMENDED SAVINGS* | $328,096 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Administrative Changes | Water Consumption | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Administrative Changes | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $31,816 Cost: - |
- | - | - | - | $31,816 | 6,263 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$31,816 6,263 MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $23,063 Cost: $4,947 |
- | - | - | - | $23,063 | 4,540 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$23,063 4,540 MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2122 INSTALL / REPAIR INSULATION ON CONDENSATE LINES |
Savings: $122 Cost: $140 |
- | - | - | - | $122 | 24 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$122 24 MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 3.4114 REPLACE CITY WATER WITH RECYCLED WATER VIA COOLING TOWER |
Savings: $103,649 Cost: $29,400 |
$(-101) | (-3,043) | - | - | - | - | $67,651 | 19,390 | - | - | $36,099 | - |
$(-101) (-3,043) kWh |
- - kW-months/year |
- - MMBtu |
$67,651 19,390 Tgal |
- - $ |
$36,099 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.4156 USE FLOW CONTROL VALVES ON EQUIPMENT TO OPTIMIZE WATER USE |
Savings: $33,724 Cost: $600 |
- | - | - | - | - | - | $21,950 | 6,291 | - | - | $11,774 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$21,950 6,291 Tgal |
- - $ |
$11,774 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $61,348 Cost: $65,000 |
$44,701 | 1,345,603 | $16,647 | 1,922 | - | - | - | - | - | - | - | - |
$44,701 1,345,603 kWh |
$16,647 1,922 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $11,367 Cost: - |
$11,367 | 342,160 | - | - | - | - | - | - | - | - | - | - |
$11,367 342,160 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $7,944 Cost: $1,500 |
$(-56) | (-1,679) | $(-24) | (-3) | $8,024 | 1,580 | - | - | - | - | - | - |
$(-56) (-1,679) kWh |
$(-24) (-3) kW-months/year |
$8,024 1,580 MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $5,813 Cost: $1,000 |
$7,820 | 235,405 | $2,793 | 322 | - | - | - | - | $(-4,800) | - | - | - |
$7,820 235,405 kWh |
$2,793 322 kW-months/year |
- - MMBtu |
- - Tgal |
$(-4,800) - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $39,230 Cost: $67,300 |
- | - | - | - | $39,230 | 7,722 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$39,230 7,722 MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $10,020 Cost: - |
- | - | - | - | $10,020 | 1,972 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$10,020 1,972 MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $328,096 Cost: $169,887 |
$63,731 | 1,918,446 | $19,416 | 2,241 | $112,275 | 22,101 | $89,601 | 25,681 | $(-4,800) | - | $47,873 | - | $63,731 1,918,446 kWh |
$19,416 2,241 kW-months/year |
$112,275 22,101 MMBtu |
$89,601 25,681 Tgal |
$(-4,800) - $ |
$47,873 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Administrative Changes | Water Consumption | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Administrative Changes | Water Consumption |