Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2020 |
Principal Product | Inkjet Printing Systems and Consumables |
NAICS | 333244 - Printing Machinery and Equipment Manufacturing |
SIC | 3555 - Printing Trades Machinery |
Sales | $100,000,000-$500,000,000 |
# of Employees | 299 |
Plant Area (Sq.Ft.) | 315,000 |
Annual Production | 533,117 Units |
Production Hrs. Annual | 6,240 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $801,378 | 17,651,504 | kWh | $0.05 |
Electricity Demand | $118,707 | 32,460 | kW-months/year | $3.66 |
Electricity Fees | $315,878 | - | $ | - |
Natural Gas | $191,113 | 46,463 | MMBtu | $4.11 |
TOTAL ENERGY COSTS | $1,521,182 | |||
RECOMMENDED SAVINGS* | $86,955 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,303 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $2,684 Cost: - |
- | - | - | - | $2,684 | 653 | - | - | - | - |
- - kWh |
- - kW-months/year |
$2,684 653 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $4,924 Cost: $1,000 |
$4,380 | 108,405 | $544 | 149 | - | - | - | - | - | - |
$4,380 108,405 kWh |
$544 149 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $4,086 Cost: - |
$3,635 | 89,974 | $451 | 124 | - | - | - | - | - | - |
$3,635 89,974 kWh |
$451 124 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 3.4116 METER RECYCLED WATER (TO REDUCE SEWER CHARGES) |
Savings: $9,326 Cost: $1,400 |
- | - | - | - | - | - | $9,326 | 1,481 | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$9,326 1,481 Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $28,713 Cost: $11,014 |
$14,027 | 347,199 | - | - | $14,686 | 3,574 | - | - | - | - |
$14,027 347,199 kWh |
- - kW-months/year |
$14,686 3,574 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $21,134 Cost: $7,500 |
$21,134 | 522,618 | - | - | - | - | - | - | - | - |
$21,134 522,618 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $12,619 Cost: $82,620 |
$7,991 | 197,803 | $3,035 | 830 | - | - | - | - | $1,593 | - |
$7,991 197,803 kWh |
$3,035 830 kW-months/year |
- - MMBtu |
- - Tgal |
$1,593 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,469 Cost: $10,920 |
$2,952 | 73,058 | $732 | 200 | - | - | - | - | $(-215) | - |
$2,952 73,058 kWh |
$732 200 kW-months/year |
- - MMBtu |
- - Tgal |
$(-215) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $86,955 Cost: $114,454 |
$54,119 | 1,339,057 | $4,762 | 1,303 | $17,370 | 4,227 | $9,326 | 1,481 | $1,378 | - | $54,119 1,339,057 kWh |
$4,762 1,303 kW-months/year |
$17,370 4,227 MMBtu |
$9,326 1,481 Tgal |
$1,378 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,303 Cost: $82,620 |
$7,991 | 197,803 | $3,035 | 830 | $2,684 | 653 | - | - | $1,593 | - | $7,991 197,803 kWh |
$3,035 830 kW-months/year |
$2,684 653 MMBtu |
- - Tgal |
$1,593 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Water Usage | Personnel Changes |