Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2002
Principal Product Circuit Assemblies
NAICS n/a
SIC 3699 - Electrical Equipment & Supplies, Nec
Sales $100,000,000-$500,000,000
# of Employees 500
Plant Area (Sq.Ft.) 300,000
Annual Production 30,000 Pieces
Production Hrs. Annual 4,680
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $852,126 15,993,683 kWh $0.05
Electricity Demand $293,885 3,008 kW-months/year $97.70
TOTAL ENERGY COSTS $1,146,011
RECOMMENDED SAVINGS* $281,193 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ $
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$13,724
Cost:
$25,919
$10,362 195,505 $3,362 31 - - $10,362
195,505
kWh
$3,362
31
kW-months/year
-
-
$
02: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$2,536
Cost:
-
$2,536 47,840 - - - - $2,536
47,840
kWh
-
-
kW-months/year
-
-
$
03: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS Savings:
$152,665
Cost:
$117,000
$152,665 2,091,298 - - - - $152,665
2,091,298
kWh
-
-
kW-months/year
-
-
$
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,740
Cost:
$290
$2,740 37,530 - - - - $2,740
37,530
kWh
-
-
kW-months/year
-
-
$
05: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,960
Cost:
$518
$1,960 26,852 - - - - $1,960
26,852
kWh
-
-
kW-months/year
-
-
$
06: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$106,637
Cost:
$10,907
$82,902 1,564,180 $23,735 221 - - $82,902
1,564,180
kWh
$23,735
221
kW-months/year
-
-
$
07: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS Savings:
$931
Cost:
$1,895
- - - - $931 - -
-
kWh
-
-
kW-months/year
$931
-
$
TOTAL RECOMMENDED Savings:
$281,193
Cost:
$156,529
$253,165 3,963,205 $27,097 252 $931 - $253,165
3,963,205
kWh
$27,097
252
kW-months/year
$931
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand One-time Revenue or Avoided Cost Electricity Usage Electricity Demand One-time Revenue or Avoided Cost