Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2003 |
Principal Product | Wallboard |
NAICS | 327420 - Gypsum Product Manufacturing |
SIC | 3275 - Gypsum Products |
Sales | $50,000,000-$100,000,000 |
# of Employees | 80 |
Plant Area (Sq.Ft.) | 871,200 |
Annual Production | 510,000 Thousand Feet |
Production Hrs. Annual | 7,488 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,489,754 | 37,630,638 | kWh | $0.07 |
Electricity Demand | $517,644 | 69,408 | kW-months/year | $7.46 |
Natural Gas | $7,189,880 | 1,334,288 | MMBtu | $5.39 |
TOTAL ENERGY COSTS | $10,197,278 | |||
RECOMMENDED SAVINGS* | $3,918,973 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $55,813 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE |
Savings: $2,080,457 Cost: $50,000 |
- | - | - | - | $2,080,457 | 385,270 | - | - |
- - kWh |
- - kW-months/year |
$2,080,457 385,270 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3417 USE WASTE HEAT WITH A CLOSED-CYCLE GAS TURBINE-GENERATOR SET TO COGENERATE ELECTRICITY AND HEAT |
Savings: $1,420,987 Cost: $5,000,000 |
$1,956,793 | 37,630,638 | $446,400 | 5,000 | $(-807,006) | (-149,446) | $(-175,200) | - |
$1,956,793 37,630,638 kWh |
$446,400 5,000 kW-months/year |
$(-807,006) (-149,446) MMBtu |
$(-175,200) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $8,639 Cost: $303 |
$8,639 | 126,797 | - | - | - | - | - | - |
$8,639 126,797 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $47,174 Cost: - |
$47,174 | 868,544 | - | - | - | - | - | - |
$47,174 868,544 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT |
Savings: $85,121 Cost: $87,198 |
$86,396 | 1,307,031 | - | - | - | - | $(-1,275) | - |
$86,396 1,307,031 kWh |
- - kW-months/year |
- - MMBtu |
$(-1,275) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $9,372 Cost: - |
$9,372 | 142,003 | - | - | - | - | - | - |
$9,372 142,003 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $25,483 Cost: $47,300 |
$20,730 | 398,649 | $4,753 | 53 | - | - | - | - |
$20,730 398,649 kWh |
$4,753 53 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $81,073 Cost: $860 |
$66,342 | 1,267,269 | $14,731 | 165 | - | - | - | - |
$66,342 1,267,269 kWh |
$14,731 165 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS |
Savings: $159,201 Cost: $2,888 |
$129,506 | 2,490,509 | $29,695 | 333 | - | - | - | - |
$129,506 2,490,509 kWh |
$29,695 333 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS |
Savings: $1,466 Cost: $3,496 |
- | - | - | - | - | - | $1,466 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$1,466 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $3,918,973 Cost: $5,192,045 |
$2,324,952 | 44,231,440 | $495,579 | 5,551 | $1,273,451 | 235,824 | $(-175,009) | - | $2,324,952 44,231,440 kWh |
$495,579 5,551 kW-months/year |
$1,273,451 235,824 MMBtu |
$(-175,009) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $55,813 Cost: $303 |
$55,813 | 995,341 | - | - | - | - | - | - | $55,813 995,341 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |