Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2003 |
Principal Product | Lumber |
NAICS | n/a |
SIC | 2421 - Sawmills And Planing Mills, General |
Sales | $10,000,000-$50,000,000 |
# of Employees | 82 |
Plant Area (Sq.Ft.) | 400,000 |
Annual Production | 48,000 Thousand Feet |
Production Hrs. Annual | 2,184 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $343,877 | 10,264,979 | kWh | $0.03 |
Electricity Demand | $248,767 | 44,985 | kW-months/year | $5.53 |
Wood | $1,281 | 1,095 | MMBtu | $1.17 |
TOTAL ENERGY COSTS | $593,925 | |||
RECOMMENDED SAVINGS* | $178,116 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $88,011 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Wood | Administrative Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Wood | Administrative Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $1,804 Cost: - |
$1,804 | 31,650 | - | - | - | - | - | - | - | - |
$1,804 31,650 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,190 Cost: $6,999 |
$1,686 | 49,591 | $1,504 | 23 | - | - | - | - | - | - |
$1,686 49,591 kWh |
$1,504 23 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4156 ESTABLISH A PREVENTATIVE MAINTENANCE PROGRAM |
Savings: $16,751 Cost: $9,663 |
$3,309 | 97,315 | $3,696 | 56 | - | - | $9,746 | - | - | - |
$3,309 97,315 kWh |
$3,696 56 kW-months/year |
- - MMBtu |
$9,746 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,308 Cost: $550 |
$1,356 | 24,630 | - | - | - | - | $(-48) | - | - | - |
$1,356 24,630 kWh |
- - kW-months/year |
- - MMBtu |
$(-48) - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,686 Cost: - |
$3,686 | 64,658 | - | - | - | - | - | - | - | - |
$3,686 64,658 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,281 Cost: $971 |
- | - | - | - | $1,281 | 1,095 | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,281 1,095 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.1291 ELIMINATE PRACTICE OF MIXING WASTE STREAMS |
Savings: $38,880 Cost: $75,000 |
- | - | - | - | - | - | - | - | $38,880 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
$38,880 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.448 INSTALL AUTOMATIC PART STORAGE / RETREVAL SYSTEM |
Savings: $80,640 Cost: $337,400 |
- | - | - | - | - | - | $80,640 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$80,640 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.441 INSTALL AUTOMATIC PACKING EQUIPMENT |
Savings: $30,576 Cost: $66,500 |
- | - | - | - | - | - | $30,576 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$30,576 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $178,116 Cost: $497,083 |
$11,841 | 267,844 | $5,200 | 79 | $1,281 | 1,095 | $120,914 | - | $38,880 | - | $11,841 267,844 kWh |
$5,200 79 kW-months/year |
$1,281 1,095 MMBtu |
$120,914 - $ |
$38,880 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $88,011 Cost: $151,163 |
$5,113 | 128,965 | $3,696 | 56 | - | - | $40,322 | - | $38,880 | - | $5,113 128,965 kWh |
$3,696 56 kW-months/year |
- - MMBtu |
$40,322 - $ |
$38,880 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Wood | Administrative Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Wood | Administrative Changes | One-time Revenue or Avoided Cost |