Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2004 |
Principal Product | Military Aircrafts |
NAICS | 336411 - Aircraft Manufacturing |
SIC | 3721 - Aircraft |
Sales | $50,000,000-$100,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 259,200 |
Annual Production | 0 Pieces |
Production Hrs. Annual | 3,952 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $230,191 | 4,985,520 | kWh | $0.05 |
Electricity Demand | $59,226 | 9,420 | kW-months/year | $6.29 |
TOTAL ENERGY COSTS | $289,417 | |||
RECOMMENDED SAVINGS* | $121,847 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $80,506 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Solid Waste (haz) | Electricity Usage | Electricity Demand | Solid Waste (haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $48,587 Cost: $63,488 |
$27,714 | 815,120 | $20,872 | 277 | - | - |
$27,714 815,120 kWh |
$20,872 277 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $19,414 Cost: - |
$2,425 | 71,313 | $16,990 | 225 | - | - |
$2,425 71,313 kWh |
$16,990 225 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $18,795 Cost: $62,620 |
$13,172 | 387,400 | $5,623 | 75 | - | - |
$13,172 387,400 kWh |
$5,623 75 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $11,169 Cost: $745 |
$11,169 | 242,810 | - | - | - | - |
$11,169 242,810 kWh |
- - kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7313 RECYCLE AIR FOR HEATING, VENTILATION AND AIR CONDITIONING |
Savings: $7,962 Cost: $31,000 |
$5,580 | 164,112 | $2,382 | 32 | - | - |
$5,580 164,112 kWh |
$2,382 32 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS |
Savings: $6,140 Cost: $779 |
$2,970 | 87,360 | $3,170 | 42 | - | - |
$2,970 87,360 kWh |
$3,170 42 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $4,543 Cost: - |
$4,543 | 133,628 | - | - | - | - |
$4,543 133,628 kWh |
- - kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $2,354 Cost: $11,495 |
$2,354 | 51,164 | - | - | - | - |
$2,354 51,164 kWh |
- - kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.5318 RECYCLE FLUORESCENT LAMPS |
Savings: $2,883 Cost: $3,496 |
- | - | - | - | $2,883 | - |
- - kWh |
- - kW-months/year |
$2,883 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $121,847 Cost: $173,623 |
$69,927 | 1,952,907 | $49,038 | 650 | $2,883 | - | $69,927 1,952,907 kWh |
$49,038 650 kW-months/year |
$2,883 - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $80,506 Cost: $94,488 |
$40,262 | 1,184,173 | $40,244 | 533 | - | - | $40,262 1,184,173 kWh |
$40,244 533 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Solid Waste (haz) | Electricity Usage | Electricity Demand | Solid Waste (haz) |