IAC logo
IAC Assessment: UF0378
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UF0378
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2006
Principal Product Pens, Mousepads
NAICS 339940 - Office Supplies (except Paper) Manufacturing
SIC 3951 - Pens And Mechanical Pencils
Sales $50,000,000-$100,000,000
# of Employees 280
Plant Area (Sq.Ft.) 146,000
Annual Production 1 Units
Production Hrs. Annual 8,400
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $173,569 7,743,640 kWh $0.02
Electricity Demand $57,271 17,057 kW-months/year $3.36
TOTAL ENERGY COSTS $253,492
RECOMMENDED SAVINGS* $122,332 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $59,231
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Solid Waste (non-haz) Electricity Usage Electricity Demand Solid Waste (non-haz)
$ kWh $ kW-months/year $ lb
01: 2.2511 INSULATE BARE EQUIPMENT Savings:
$7,955
Cost:
$7,050
$7,955 130,410 - - - - $7,955
130,410
kWh
-
-
kW-months/year
-
-
lb
02: 2.4235 REMOVE OR CLOSE OFF UNNEEDED COMPRESSED AIR LINES Savings:
$10,965
Cost:
$5,044
$10,965 158,912 - - - - $10,965
158,912
kWh
-
-
kW-months/year
-
-
lb
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,337
Cost:
$598
$3,337 48,369 - - - - $3,337
48,369
kWh
-
-
kW-months/year
-
-
lb
04: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS Savings:
$10,260
Cost:
$2,640
$8,989 147,360 $1,271 31 - - $8,989
147,360
kWh
$1,271
31
kW-months/year
-
-
lb
05: 2.7131 ADD AREA LIGHTING SWITCHES Savings:
$4,427
Cost:
$15,444
$4,427 72,576 - - - - $4,427
72,576
kWh
-
-
kW-months/year
-
-
lb
06: 2.7292 LOWER CEILING TO REDUCE CONDITIONED SPACE Savings:
$55,146
Cost:
$7,392
$55,146 799,224 - - - - $55,146
799,224
kWh
-
-
kW-months/year
-
-
lb
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$26,845
Cost:
$12,045
$23,596 386,814 $3,249 78 - - $23,596
386,814
kWh
$3,249
78
kW-months/year
-
-
lb
08: 3.1291 ELIMINATE PRACTICE OF MIXING WASTE STREAMS Savings:
$3,397
Cost:
$507
- - - - $3,397 197,126 -
-
kWh
-
-
kW-months/year
$3,397
197,126
lb
TOTAL RECOMMENDED Savings:
$122,332
Cost:
$50,720
$114,415 1,743,665 $4,520 109 $3,397 197,126 $114,415
1,743,665
kWh
$4,520
109
kW-months/year
$3,397
197,126
lb
TOTAL IMPLEMENTED Savings:
$59,231
Cost:
$36,278
$51,314 814,031 $4,520 109 $3,397 197,126 $51,314
814,031
kWh
$4,520
109
kW-months/year
$3,397
197,126
lb
Savings
Cost
$ kWh $ kW-months/year $ lb
Electricity Usage Electricity Demand Solid Waste (non-haz) Electricity Usage Electricity Demand Solid Waste (non-haz)