Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Florida |
---|---|
Assessment Year | 2007 |
Principal Product | Reinforced hoses and rubber seals |
NAICS | 326291 - Rubber Product Manufacturing for Mechanical Use |
SIC | 3061 - Mechanical Rubber Goods |
Sales | $10,000,000-$50,000,000 |
# of Employees | 175 |
Plant Area (Sq.Ft.) | 86,000 |
Annual Production | 8,700,000 Pieces |
Production Hrs. Annual | 4,290 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $337,825 | 7,107,200 | kWh | $0.05 |
Electricity Demand | $146,889 | 15,580 | kW-months/year | $9.43 |
Natural Gas | $17,136 | 20,563 | MMBtu | $0.83 |
TOTAL ENERGY COSTS | $501,850 | |||
RECOMMENDED SAVINGS* | $84,125 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,982 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $7,913 Cost: $36,935 |
$2,643 | 110,256 | $5,270 | 23 | - | - | - | - | - | - |
$2,643 110,256 kWh |
$5,270 23 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7145 INSTALL SKYLIGHTS |
Savings: $6,200 Cost: $14,564 |
$2,992 | 62,578 | $3,208 | 28 | - | - | - | - | - | - |
$2,992 62,578 kWh |
$3,208 28 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $3,038 Cost: - |
$1,871 | 38,938 | $1,167 | 10 | - | - | - | - | - | - |
$1,871 38,938 kWh |
$1,167 10 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $1,673 Cost: $2,571 |
$1,673 | 41,913 | - | - | - | - | - | - | - | - |
$1,673 41,913 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.1181 ELIMINATE A BY-PRODUCT |
Savings: $3,032 Cost: $158 |
- | - | - | - | $3,032 | 259 | - | - | - | - |
- - kWh |
- - kW-months/year |
$3,032 259 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 4.424 IMPROVE SPACE COMFORT CONDITIONING |
Savings: $13,160 Cost: $26,800 |
$13,160 | 105,848 | - | - | - | - | - | - | - | - |
$13,160 105,848 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,239 Cost: $638 |
$2,239 | 46,162 | - | - | - | - | - | - | - | - |
$2,239 46,162 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.111 ADD EQUIPMENT/ OPERATORS TO REDUCE PRODUCTION BOTTLENECK |
Savings: $5,850 Cost: $957 |
- | - | - | - | - | - | $5,850 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$5,850 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.445 INSTALL EQUIPMENT TO MOVE PRODUCT |
Savings: $32,175 Cost: $1,260 |
- | - | - | - | - | - | $32,175 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$32,175 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 4.445 INSTALL EQUIPMENT TO MOVE PRODUCT |
Savings: $8,845 Cost: $43,500 |
- | - | - | - | - | - | - | - | $8,845 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
$8,845 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $84,125 Cost: $127,383 |
$24,578 | 405,695 | $9,645 | 61 | $3,032 | 259 | $38,025 | - | $8,845 | - | $24,578 405,695 kWh |
$9,645 61 kW-months/year |
$3,032 259 MMBtu |
$38,025 - $ |
$8,845 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,982 Cost: $3,367 |
$5,783 | 127,013 | $1,167 | 10 | $3,032 | 259 | - | - | - | - | $5,783 127,013 kWh |
$1,167 10 kW-months/year |
$3,032 259 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost |