IAC Center University of Florida
Assessment Year 2019
Principal Product Roofing Insulation and Composite Materials
NAICS 324122 - Asphalt Shingle and Coating Materials Manufacturing
SIC 2952 - Asphalt Felts And Coatings
Sales $53,000,000
# of Employees 132
Plant Area (Sq.Ft.) 400,000
Annual Production 8,300,000 not found
Production Hrs. Annual 8,760
Location (State) FL
Source Yearly Cost Usage
Electricity Usage $529,340 9,298,571
Electricity Demand $112,366 16,722
Electricity Fees $78,520 -
Natural Gas $817,470 373,302
TOTAL ENERGY COSTS $1,565,482
RECOMMENDED SAVINGS* $108,567 *Non-energy impacts
included in savings.
IMPLEMENTED SAVINGS* -
#|Description Status Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes Ancillary Material Cost Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes Ancillary Material Cost
$ kWh $ kW/month $ MMBtu $ $ $ $ $ $
01: 2.8212 REDUCE DELIVERY SCHEDULES Savings:
$43,506
Cost:
-
- - - - - - $40,000 - $3,506 - - - -
-
kWh
-
-
kW/month
-
-
MMBtu
$40,000
-
$
$3,506
-
$
-
-
$
02: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$19,621
Cost:
$2,800
- - - - $19,621 8,959 - - - - - - -
-
kWh
-
-
kW/month
$19,621
8,959
MMBtu
-
-
$
-
-
$
-
-
$
03: 2.2411 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT COMBUSTION AIR Savings:
$14,666
Cost:
$30,000
- - - - $14,666 6,697 - - - - - - -
-
kWh
-
-
kW/month
$14,666
6,697
MMBtu
-
-
$
-
-
$
-
-
$
04: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS Savings:
$14,533
Cost:
$1,600
- - - - $14,533 6,636 - - - - - - -
-
kWh
-
-
kW/month
$14,533
6,636
MMBtu
-
-
$
-
-
$
-
-
$
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$7,991
Cost:
$4,959
$6,879 120,888 $1,112 166 - - - - - - - - $6,879
120,888
kWh
$1,112
166
kW/month
-
-
MMBtu
-
-
$
-
-
$
-
-
$
06: 2.2131 INSULATE STEAM / HOT WATER LINES Savings:
$2,925
Cost:
$1,308
- - - - $2,925 1,336 - - - - - - -
-
kWh
-
-
kW/month
$2,925
1,336
MMBtu
-
-
$
-
-
$
-
-
$
07: 2.4222 INSTALL ADEQUATE DRYERS ON AIR LINES TO ELIMINATE BLOWDOWN Savings:
$2,600
Cost:
$9,464
$2,600 45,693 - - - - - - - - - - $2,600
45,693
kWh
-
-
kW/month
-
-
MMBtu
-
-
$
-
-
$
-
-
$
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$1,990
Cost:
-
$1,990 34,969 - - - - - - - - - - $1,990
34,969
kWh
-
-
kW/month
-
-
MMBtu
-
-
$
-
-
$
-
-
$
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$735
Cost:
-
$537 9,442 - - - - $90 - - - $108 - $537
9,442
kWh
-
-
kW/month
-
-
MMBtu
$90
-
$
-
-
$
$108
-
$
TOTAL RECOMMENDED Savings:
$108,567
Cost:
$50,131
$12,006 210,992 $1,112 166 $51,745 23,628 $40,090 - $3,506 - $108 - -
-
kWh
-
-
kW/month
-
-
MMBtu
-
-
$
-
-
$
-
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - - - - - -
-
kWh
-
-
kW/month
-
-
MMBtu
-
-
$
-
-
$
-
-
$
$ kWh $ kW/month $ MMBtu $ $ $ $ $ $
Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes Ancillary Material Cost Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes Ancillary Material Cost
Back to Top