Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Louisville
Assessment Year 2023
Principal Product Filters and Filter Media
NAICS 333413 - Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing
SIC 3564 - Blowers And Fans
Sales $50,000,000-$100,000,000
# of Employees 143
Plant Area (Sq.Ft.) 232,256
Annual Production 10,617,486 Pieces
Production Hrs. Annual 6,240
Location (State) KY
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $393,219 4,846,682 kWh $0.08
Electricity Demand $148,679 10,867 kW-months/year $13.68
Electricity Fees $53,166 - $ -
Natural Gas $128,094 14,709 MMBtu $8.71
TOTAL ENERGY COSTS $748,047
RECOMMENDED SAVINGS* $313,508 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$145,022
Cost:
$23,878
$121,046 1,494,397 $23,976 1,752 $121,046
1,494,397
kWh
$23,976
1,752
kW-months/year
02: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$4,283
Cost:
-
$2,598 32,021 $1,685 120 $2,598
32,021
kWh
$1,685
120
kW-months/year
03: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$159,497
Cost:
$1,065,693
$121,666 1,499,617 $37,831 2,764 $121,666
1,499,617
kWh
$37,831
2,764
kW-months/year
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,462
Cost:
-
$2,462 30,394 - - $2,462
30,394
kWh
-
-
kW-months/year
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,694
Cost:
$540
$1,694 20,908 - - $1,694
20,908
kWh
-
-
kW-months/year
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$550
Cost:
$2,438
$550 6,776 - - $550
6,776
kWh
-
-
kW-months/year
TOTAL RECOMMENDED Savings:
$313,508
Cost:
$1,092,549
$250,016 3,084,113 $63,492 4,636 $250,016
3,084,113
kWh
$63,492
4,636
kW-months/year
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand