IAC logo
IAC Assessment: UL2314
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UL2314
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Louisville
Assessment Year 2023
Principal Product Repair of industrial machines
NAICS 332710 - Machine Shops
SIC 3599 - Industrial Machinery, Nec
Sales $50,000,000-$100,000,000
# of Employees 230
Plant Area (Sq.Ft.) 80,000
Annual Production 10,000 Units
Production Hrs. Annual 8,736
Location (State) KY
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $74,417 2,515,800 kWh $0.03
Electricity Demand $155,187 5,687 kW-months/year $27.29
Electricity Fees $37,168 - $ -
Natural Gas $79,113 6,065 MMBtu $13.04
TOTAL ENERGY COSTS $345,885
RECOMMENDED SAVINGS* $125,348 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Natural Gas Electricity Usage Electricity Demand Electricity Fees Natural Gas
$ kWh $ kW-months/year $ $ $ MMBtu
01: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$29,804
Cost:
$13,936
- - - - $29,804 - - - -
-
kWh
-
-
kW-months/year
$29,804
-
$
-
-
MMBtu
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,821
Cost:
$13,461
$1,261 42,064 $1,560 58 - - - - $1,261
42,064
kWh
$1,560
58
kW-months/year
-
-
$
-
-
MMBtu
03: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$20,576
Cost:
$15,000
- - - - - - $20,576 1,577 -
-
kWh
-
-
kW-months/year
-
-
$
$20,576
1,577
MMBtu
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,358
Cost:
-
$1,358 45,267 - - - - - - $1,358
45,267
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$5,061
Cost:
$4,320
$5,061 168,688 - - - - - - $5,061
168,688
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$3,398
Cost:
$6,825
$3,398 114,856 - - - - - - $3,398
114,856
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
07: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$54,095
Cost:
$476,338
$20,369 688,593 $33,726 1,236 - - - - $20,369
688,593
kWh
$33,726
1,236
kW-months/year
-
-
$
-
-
MMBtu
08: 2.2692 USE OUTSIDE COLD WATER SOURCE AS A SUPPLY OF COOLING WATER Savings:
$2,765
Cost:
-
$2,765 92,154 - - - - - - $2,765
92,154
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
09: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$5,470
Cost:
$15,600
- - - - - - $5,470 419 -
-
kWh
-
-
kW-months/year
-
-
$
$5,470
419
MMBtu
TOTAL RECOMMENDED Savings:
$125,348
Cost:
$545,480
$34,212 1,151,622 $35,286 1,294 $29,804 - $26,046 1,996 $34,212
1,151,622
kWh
$35,286
1,294
kW-months/year
$29,804
-
$
$26,046
1,996
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ $ $ MMBtu
Electricity Usage Electricity Demand Electricity Fees Natural Gas Electricity Usage Electricity Demand Electricity Fees Natural Gas