Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Michigan |
---|---|
Assessment Year | 2001 |
Principal Product | Phamaceuticals |
NAICS | n/a |
SIC | 2834 - Pharmaceutical Preparations |
Sales | $100,000,000-$500,000,000 |
# of Employees | 480 |
Plant Area (Sq.Ft.) | 450,000 |
Annual Production | 0 Units |
Production Hrs. Annual | 5,760 |
Location (State) | MI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,416,772 | 35,194,759 | kWh | $0.07 |
Electricity Demand | $271,270 | 36,192 | kW-months/year | $7.50 |
Natural Gas | $539,416 | 101,055 | MMBtu | $5.34 |
TOTAL ENERGY COSTS | $3,227,458 | |||
RECOMMENDED SAVINGS* | $503,714 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $101,862 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $81,576 Cost: $80,632 |
$81,576 | 1,130,180 | - | - | - | - | - | - |
$81,576 1,130,180 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $20,468 Cost: $9,600 |
- | - | $20,468 | 283,564 | - | - | - | - |
- - kWh |
$20,468 283,564 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $82,700 Cost: $8,000 |
$78,424 | 1,090,000 | - | - | - | - | $4,276 | 786 |
$78,424 1,090,000 kWh |
- - kW-months/year |
- - $ |
$4,276 786 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3113 MAKE ICE DURING OFF PEAK HOURS FOR COOLING |
Savings: $293,000 Cost: $360,000 |
- | - | $293,000 | 16,440 | - | - | - | - |
- - kWh |
$293,000 16,440 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $20,286 Cost: $8,250 |
- | - | - | - | $20,286 | - | - | - |
- - kWh |
- - kW-months/year |
$20,286 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $5,684 Cost: $1,000 |
$5,684 | 72,869 | - | - | - | - | - | - |
$5,684 72,869 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $503,714 Cost: $467,482 |
$165,684 | 2,293,049 | $313,468 | 300,004 | $20,286 | - | $4,276 | 786 | $165,684 2,293,049 kWh |
$313,468 300,004 kW-months/year |
$20,286 - $ |
$4,276 786 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $101,862 Cost: $88,882 |
$81,576 | 1,130,180 | - | - | $20,286 | - | - | - | $81,576 1,130,180 kWh |
- - kW-months/year |
$20,286 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |