Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Michigan |
---|---|
Assessment Year | 2008 |
Principal Product | Recycled Boxboard |
NAICS | 322130 - Paperboard Mills |
SIC | 2631 - Paperboard Mills |
Sales | $10,000,000-$50,000,000 |
# of Employees | 101 |
Plant Area (Sq.Ft.) | 200,000 |
Annual Production | 70,000 Tons |
Production Hrs. Annual | 8,400 |
Location (State) | MI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $852,923 | 39,499,200 | kWh | $0.02 |
Electricity Demand | $929,560 | 63,600 | kW-months/year | $14.62 |
Natural Gas | $1,889,489 | 240,625 | MMBtu | $7.85 |
Fuel Oil #6 | $1,695,881 | 274,718 | MMBtu | $6.17 |
TOTAL ENERGY COSTS | $5,367,853 | |||
RECOMMENDED SAVINGS* | $245,191 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $79,804 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $101,548 Cost: $18,088 |
- | - | - | - | $101,548 | 12,936 |
- - kWh |
- - kW-months/year |
$101,548 12,936 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $79,804 Cost: $53,414 |
- | - | - | - | $79,804 | 10,166 |
- - kWh |
- - kW-months/year |
$79,804 10,166 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $31,965 Cost: $59,142 |
- | - | - | - | $31,965 | 4,072 |
- - kWh |
- - kW-months/year |
$31,965 4,072 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $13,835 Cost: $4,800 |
$7,032 | 325,722 | $6,803 | 465 | - | - |
$7,032 325,722 kWh |
$6,803 465 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $8,572 Cost: $5,000 |
- | - | - | - | $8,572 | 1,092 |
- - kWh |
- - kW-months/year |
$8,572 1,092 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,111 Cost: $8,160 |
$3,106 | 143,875 | $3,005 | 206 | - | - |
$3,106 143,875 kWh |
$3,005 206 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $3,356 Cost: $515 |
$1,704 | 78,885 | $1,652 | 113 | - | - |
$1,704 78,885 kWh |
$1,652 113 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $245,191 Cost: $149,119 |
$11,842 | 548,482 | $11,460 | 784 | $221,889 | 28,266 | $11,842 548,482 kWh |
$11,460 784 kW-months/year |
$221,889 28,266 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $79,804 Cost: $53,414 |
- | - | - | - | $79,804 | 10,166 | - - kWh |
- - kW-months/year |
$79,804 10,166 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |