Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Utah
Assessment Year 2005
Principal Product Printed Material
NAICS 323111 - Commercial Printing (except Screen and Books)
SIC 2752 - Commercial Printing, Lithographic
Sales $5,000,000-$10,000,000
# of Employees 75
Plant Area (Sq.Ft.) 120,000
Annual Production 25,000 Thousand Feet
Production Hrs. Annual 2,500
Location (State) UT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $17,073 620,240 kWh $0.03
Electricity Demand $34,159 3,466 kW-months/year $9.86
Natural Gas $46,598 7,867 MMBtu $5.92
TOTAL ENERGY COSTS $97,830
RECOMMENDED SAVINGS* $16,710 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER Savings:
$2,270
Cost:
$7,000
- - $2,270 240 -
-
kWh
$2,270
240
kW-months/year
02: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$1,360
Cost:
$420
$710 25,210 $650 50 $710
25,210
kWh
$650
50
kW-months/year
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$330
Cost:
$180
$80 2,710 $250 25 $80
2,710
kWh
$250
25
kW-months/year
04: 2.6127 MAINTAIN AIR FILTERS BY CLEANING OR REPLACEMENT Savings:
$250
Cost:
$75
$130 4,630 $120 10 $130
4,630
kWh
$120
10
kW-months/year
05: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$12,500
Cost:
$15,290
- - $12,500 1,030 -
-
kWh
$12,500
1,030
kW-months/year
TOTAL RECOMMENDED Savings:
$16,710
Cost:
$22,965
$920 32,550 $15,790 1,355 $920
32,550
kWh
$15,790
1,355
kW-months/year
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand