Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Utah |
---|---|
Assessment Year | 2021 |
Principal Product | Fiberglass Insulation |
NAICS | 327211 - Flat Glass Manufacturing |
SIC | 3211 - Flat Glass |
Sales | $10,000,000-$50,000,000 |
# of Employees | 41 |
Plant Area (Sq.Ft.) | 300,000 |
Annual Production | 74,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | UT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,286,699 | 39,148,800 | kWh | $0.03 |
Electricity Demand | $824,761 | 60,040 | kW-months/year | $13.74 |
Natural Gas | $375,950 | 91,671 | MMBtu | $4.10 |
TOTAL ENERGY COSTS | $2,487,410 | |||
RECOMMENDED SAVINGS* | $79,392 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $59,220 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $26,862 Cost: $88,688 |
$17,399 | 528,844 | $9,463 | 689 |
$17,399 528,844 kWh |
$9,463 689 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $22,604 Cost: $16,880 |
$14,383 | 437,176 | $8,221 | 599 |
$14,383 437,176 kWh |
$8,221 599 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $20,172 Cost: $4,900 |
$12,922 | 391,580 | $7,249 | 528 |
$12,922 391,580 kWh |
$7,249 528 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $8,017 Cost: $14,979 |
$5,101 | 155,052 | $2,916 | 212 |
$5,101 155,052 kWh |
$2,916 212 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,737 Cost: $860 |
$1,105 | 33,590 | $632 | 46 |
$1,105 33,590 kWh |
$632 46 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $79,392 Cost: $126,307 |
$50,910 | 1,546,242 | $28,481 | 2,074 | $50,910 1,546,242 kWh |
$28,481 2,074 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $59,220 Cost: $121,407 |
$37,988 | 1,154,662 | $21,232 | 1,546 | $37,988 1,154,662 kWh |
$21,232 1,546 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |