Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Utah
Assessment Year 2022
Principal Product Airplane frames and parts
NAICS 336413 - Other Aircraft Parts and Auxiliary Equipment Manufacturing
SIC 3728 - Aircraft Parts And Equipment, Nec
Sales $10,000,000-$50,000,000
# of Employees 400
Plant Area (Sq.Ft.) 403,000
Annual Production 30 Units
Production Hrs. Annual 8,424
Location (State) UT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $680,744 18,805,839 kWh $0.04
Electricity Demand $924,482 52,025 kW-months/year $17.77
Electricity Fees $152,656 - $ -
Natural Gas $292,781 59,612 MMBtu $4.91
TOTAL ENERGY COSTS $2,050,663
RECOMMENDED SAVINGS* $111,286 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $44,227
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.1243 USE HEAT FROM BOILER BLOWDOWN TO PREHEAT BOILER FEED WATER Savings:
$39,902
Cost:
$83,130
- - - - $39,902 8,126 -
-
kWh
-
-
kW-months/year
$39,902
8,126
MMBtu
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$37,721
Cost:
$113,682
$22,198 613,216 $15,523 874 - - $22,198
613,216
kWh
$15,523
874
kW-months/year
-
-
MMBtu
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$25,369
Cost:
$20,108
- - - - $25,369 5,167 -
-
kWh
-
-
kW-months/year
$25,369
5,167
MMBtu
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$5,610
Cost:
$23,208
$3,087 85,281 $2,523 142 - - $3,087
85,281
kWh
$2,523
142
kW-months/year
-
-
MMBtu
05: 2.7272 INSTALL HEAT PIPES / RAISE COOLING SETPOINT Savings:
$1,788
Cost:
$2,208
$1,434 39,607 $354 20 - - $1,434
39,607
kWh
$354
20
kW-months/year
-
-
MMBtu
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$896
Cost:
$1,796
$535 14,866 $361 20 - - $535
14,866
kWh
$361
20
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$111,286
Cost:
$244,132
$27,254 752,970 $18,761 1,056 $65,271 13,293 $27,254
752,970
kWh
$18,761
1,056
kW-months/year
$65,271
13,293
MMBtu
TOTAL IMPLEMENTED Savings:
$44,227
Cost:
$138,686
$25,820 713,363 $18,407 1,036 - - $25,820
713,363
kWh
$18,407
1,036
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas