Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Utah
Assessment Year 2023
Principal Product Medical Devices
NAICS 339112 - Surgical and Medical Instrument Manufacturing
SIC 3841 - Surgical And Medical Instruments
Sales $100,000,000-$500,000,000
# of Employees 500
Plant Area (Sq.Ft.) 650,000
Annual Production 500,000,000 Units
Production Hrs. Annual 8,616
Location (State) UT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,767,347 48,333,600 kWh $0.04
Electricity Demand $1,200,366 75,510 kW-months/year $15.90
Natural Gas $398,097 52,255 MMBtu $7.62
TOTAL ENERGY COSTS $3,365,810
RECOMMENDED SAVINGS* $62,598 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $36,935
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Usage Electricity Usage Electricity Demand Natural Gas Water Usage
$ kWh $ kW-months/year $ MMBtu $ Tgal
01: 2.3112 STORE HEATED/ COOLED WATER FOR USE DURING PEAK DEMAND PERIODS Savings:
$19,636
Cost:
$127,500
$5,167 - $14,469 502 - - - - $5,167
-
kWh
$14,469
502
kW-months/year
-
-
MMBtu
-
-
Tgal
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$14,519
Cost:
$14,890
$11,912 322,400 $2,607 164 - - - - $11,912
322,400
kWh
$2,607
164
kW-months/year
-
-
MMBtu
-
-
Tgal
03: 2.7311 VENTILATION SYSTEM TO SHUT OFF WHEN ROOM IS NOT IN USE Savings:
$6,518
Cost:
$19,160
$2,291 61,920 $3,983 251 $244 32 - - $2,291
61,920
kWh
$3,983
251
kW-months/year
$244
32
MMBtu
-
-
Tgal
04: 2.7252 UTILIZE AN EVAPORATIVE AIR PRE-COOLER OR OTHER HEAT EXCHANGER IN AC SYSTEM Savings:
$6,026
Cost:
$30,128
$1,240 33,506 $5,535 348 - - $(-749) (-138) $1,240
33,506
kWh
$5,535
348
kW-months/year
-
-
MMBtu
$(-749)
(-138)
Tgal
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$15,898
Cost:
$263,547
$15,898 429,699 - - - - - - $15,898
429,699
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
TOTAL RECOMMENDED Savings:
$62,598
Cost:
$455,225
$36,508 847,525 $26,595 1,264 $244 32 $(-749) (-138) $36,508
847,525
kWh
$26,595
1,264
kW-months/year
$244
32
MMBtu
$(-749)
(-138)
Tgal
TOTAL IMPLEMENTED Savings:
$36,935
Cost:
$297,597
$30,101 814,019 $6,590 415 $244 32 - - $30,101
814,019
kWh
$6,590
415
kW-months/year
$244
32
MMBtu
-
-
Tgal
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal
Electricity Usage Electricity Demand Natural Gas Water Usage Electricity Usage Electricity Demand Natural Gas Water Usage