Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Utah |
---|---|
Assessment Year | 2024 |
Principal Product | Salt, Sulfate of Potash, and Magnesium Chloride |
NAICS | 325180 - Other Basic Inorganic Chemical Manufacturing |
SIC | 2812 - Alkalies And Chlorine |
Sales | $100,000,000-$500,000,000 |
# of Employees | 350 |
Plant Area (Sq.Ft.) | 175,000 |
Annual Production | 325,000 Tons |
Production Hrs. Annual | 8,030 |
Location (State) | UT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,268,810 | 76,908,788 | kWh | $0.03 |
Electricity Demand | $2,044,543 | 131,739 | kW-months/year | $15.52 |
Electricity Fees | $739,077 | - | $ | - |
Natural Gas | $7,083,780 | 1,636,512 | MMBtu | $4.33 |
TOTAL ENERGY COSTS | $12,136,210 | |||
RECOMMENDED SAVINGS* | $2,196,860 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1223 INSTALL SMALLER BOILER (INCREASE HIGH FIRE DUTY CYCLE) |
Savings: $158,000 Cost: $725,000 |
- | - | - | - | $158,000 | 36,400 | - | - |
- - kWh |
- - kW-months/year |
$158,000 36,400 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $25,800 Cost: $6,200 |
- | - | - | - | $25,800 | 5,970 | - | - |
- - kWh |
- - kW-months/year |
$25,800 5,970 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1116 IMPROVE COMBUSTION CONTROL CAPABILITY |
Savings: $12,600 Cost: $54,500 |
- | - | - | - | $12,600 | 2,900 | - | - |
- - kWh |
- - kW-months/year |
$12,600 2,900 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3417 USE WASTE HEAT WITH A CLOSED-CYCLE GAS TURBINE-GENERATOR SET TO COGENERATE ELECTRICITY AND HEAT |
Savings: $1,690,000 Cost: $23,500,000 |
$1,600,000 | 53,900,000 | $1,250,000 | 80,500 | $(-1,080,000) | 251,000 | $(-80,000) | - |
$1,600,000 53,900,000 kWh |
$1,250,000 80,500 kW-months/year |
$(-1,080,000) 251,000 MMBtu |
$(-80,000) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $7,890 Cost: $11,500 |
$4,420 | 150,000 | $3,470 | 224 | - | - | - | - |
$4,420 150,000 kWh |
$3,470 224 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,570 Cost: $5,140 |
$1,550 | 52,700 | $1,020 | 66 | - | - | - | - |
$1,550 52,700 kWh |
$1,020 66 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $120,000 Cost: $198,000 |
- | - | $120,000 | 7,720 | - | - | - | - |
- - kWh |
$120,000 7,720 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $180,000 Cost: $20,000 |
- | - | $180,000 | 1,800 | - | - | - | - |
- - kWh |
$180,000 1,800 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $2,196,860 Cost: $24,520,340 |
$1,605,970 | 54,102,700 | $1,554,490 | 90,310 | $(-883,600) | 296,270 | $(-80,000) | - | $1,605,970 54,102,700 kWh |
$1,554,490 90,310 kW-months/year |
$(-883,600) 296,270 MMBtu |
$(-80,000) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes |