Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Utah |
---|---|
Assessment Year | 2025 |
Principal Product | Ice rink |
NAICS | 713940 - Fitness and Recreational Sports Centers |
SIC | 7999 - Amusement And Recreation, Nec |
Sales | $1,000,000-$5,000,000 |
# of Employees | 50 |
Plant Area (Sq.Ft.) | 120,000 |
Annual Production | 1 Units |
Production Hrs. Annual | 6,032 |
Location (State) | UT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $107,920 | 2,355,840 | kWh | $0.05 |
Electricity Demand | $64,696 | 4,387 | kW-months/year | $14.75 |
Electricity Fees | $10,750 | - | $ | - |
Natural Gas | $71,970 | 7,470 | MMBtu | $9.63 |
TOTAL ENERGY COSTS | $255,336 | |||
RECOMMENDED SAVINGS* | $66,391 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS |
Savings: $12,948 Cost: $57,090 |
$(-60) | (-1,350) | $(-382) | (-26) | $13,390 | 1,390 | - | - |
$(-60) (-1,350) kWh |
$(-382) (-26) kW-months/year |
$13,390 1,390 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE |
Savings: $4,322 Cost: $21,080 |
$660 | 14,420 | $292 | 20 | $3,370 | 350 | - | - |
$660 14,420 kWh |
$292 20 kW-months/year |
$3,370 350 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE |
Savings: $2,977 Cost: $13,970 |
$463 | 10,020 | $202 | 14 | $2,311 | 240 | - | - |
$463 10,020 kWh |
$202 14 kW-months/year |
$2,311 240 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $29,270 Cost: $414,260 |
$29,270 | 633,600 | - | - | - | - | - | - |
$29,270 633,600 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $16,874 Cost: $41,100 |
$4,200 | 90,390 | $2,194 | 149 | - | - | $10,480 | - |
$4,200 90,390 kWh |
$2,194 149 kW-months/year |
- - MMBtu |
$10,480 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $66,391 Cost: $547,500 |
$34,533 | 747,080 | $2,306 | 156 | $19,071 | 1,980 | $10,480 | - | $34,533 747,080 kWh |
$2,306 156 kW-months/year |
$19,071 1,980 MMBtu |
$10,480 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes |