Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2014 |
Principal Product | compact construction equipment |
NAICS | 333120 - Construction Machinery Manufacturing |
SIC | 3531 - Construction Machinery |
Sales | $100,000,000-$500,000,000 |
# of Employees | 450 |
Plant Area (Sq.Ft.) | 405,000 |
Annual Production | 46,000 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $751,712 | 11,815,579 | kWh | $0.06 |
Electricity Demand | $331,140 | 25,953 | kW-months/year | $12.76 |
Natural Gas | $502,679 | 81,651 | MMBtu | $6.16 |
TOTAL ENERGY COSTS | $1,647,225 | |||
RECOMMENDED SAVINGS* | $136,181 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $71,004 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $46,648 Cost: $27,260 |
$33,659 | 529,227 | $12,989 | 1,018 | - | - |
$33,659 529,227 kWh |
$12,989 1,018 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $15,358 Cost: $6,250 |
$11,084 | 174,283 | $4,274 | 335 | - | - |
$11,084 174,283 kWh |
$4,274 335 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,736 Cost: $800 |
- | - | - | - | $2,736 | 445 |
- - kWh |
- - kW-months/year |
$2,736 445 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $13,050 Cost: $225 |
$9,414 | 148,020 | $3,636 | 285 | - | - |
$9,414 148,020 kWh |
$3,636 285 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $4,680 Cost: $3,200 |
$1,477 | 23,224 | $3,203 | 251 | - | - |
$1,477 23,224 kWh |
$3,203 251 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $18,680 Cost: $5,175 |
$5,908 | 92,898 | $12,772 | 1,001 | - | - |
$5,908 92,898 kWh |
$12,772 1,001 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2442 PREHEAT COMBUSTION AIR WITH WASTE HEAT |
Savings: $9,345 Cost: $35,000 |
- | - | - | - | $9,345 | 1,523 |
- - kWh |
- - kW-months/year |
$9,345 1,523 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $14,378 Cost: $3,000 |
$14,378 | 226,067 | - | - | - | - |
$14,378 226,067 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.1224 REPLACE BOILER |
Savings: $11,306 Cost: $16,000 |
- | - | - | - | $11,306 | 1,827 |
- - kWh |
- - kW-months/year |
$11,306 1,827 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $136,181 Cost: $96,910 |
$75,920 | 1,193,719 | $36,874 | 2,890 | $23,387 | 3,795 | $75,920 1,193,719 kWh |
$36,874 2,890 kW-months/year |
$23,387 3,795 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $71,004 Cost: $43,485 |
$43,073 | 677,247 | $16,625 | 1,303 | $11,306 | 1,827 | $43,073 677,247 kWh |
$16,625 1,303 kW-months/year |
$11,306 1,827 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |