Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Wisconsin, Milwaukee
Assessment Year 2018
Principal Product Hydraulic valves
NAICS 332912 - Fluid Power Valve and Hose Fitting Manufacturing
SIC 3492 - Fluid Power Valves & Hose Fittings
Sales $50,000,000-$100,000,000
# of Employees 346
Plant Area (Sq.Ft.) 250,000
Annual Production 7,612,080 Pieces
Production Hrs. Annual 4,800
Location (State) WI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $792,880 12,263,920 kWh $0.06
Electricity Demand $425,327 30,821 kW-months/year $13.80
Electricity Fees $73,178 - $ -
Natural Gas $99,760 23,377 MMBtu $4.27
TOTAL ENERGY COSTS $1,391,145
RECOMMENDED SAVINGS* $142,101 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $33,325
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$61,479
Cost:
$72,000
$61,479 950,951 - - - - $61,479
950,951
kWh
-
-
kW-months/year
-
-
MMBtu
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$33,220
Cost:
$39,050
$23,284 360,205 $9,936 720 - - $23,284
360,205
kWh
$9,936
720
kW-months/year
-
-
MMBtu
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$31,440
Cost:
$42,800
$22,029 340,800 $9,411 682 - - $22,029
340,800
kWh
$9,411
682
kW-months/year
-
-
MMBtu
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$6,804
Cost:
$2,793
$5,024 77,707 $1,780 129 - - $5,024
77,707
kWh
$1,780
129
kW-months/year
-
-
MMBtu
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,936
Cost:
$4,135
$2,936 45,421 - - - - $2,936
45,421
kWh
-
-
kW-months/year
-
-
MMBtu
06: 2.7231 USE RADIANT HEATER FOR SPOT HEATING Savings:
$2,460
Cost:
$3,660
- - - - $2,460 577 -
-
kWh
-
-
kW-months/year
$2,460
577
MMBtu
07: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,885
Cost:
$1,980
$1,319 20,429 $566 41 - - $1,319
20,429
kWh
$566
41
kW-months/year
-
-
MMBtu
08: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD Savings:
$1,390
Cost:
$2,469
$1,390 21,054 - - - - $1,390
21,054
kWh
-
-
kW-months/year
-
-
MMBtu
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$487
Cost:
$864
$377 5,821 $110 8 - - $377
5,821
kWh
$110
8
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$142,101
Cost:
$169,751
$117,838 1,822,388 $21,803 1,580 $2,460 577 $117,838
1,822,388
kWh
$21,803
1,580
kW-months/year
$2,460
577
MMBtu
TOTAL IMPLEMENTED Savings:
$33,325
Cost:
$44,780
$23,348 361,229 $9,977 723 - - $23,348
361,229
kWh
$9,977
723
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas