Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Wisconsin, Milwaukee |
---|---|
Assessment Year | 2018 |
Principal Product | sewage |
NAICS | 221320 - Sewage Treatment Facilities |
SIC | 4952 - Sewerage Systems |
Sales | <$500,000 |
# of Employees | 22 |
Plant Area (Sq.Ft.) | 1,265,000 |
Annual Production | 7,665,000 Thousand Gallons |
Production Hrs. Annual | 8,736 |
Location (State) | WI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $299,821 | 6,271,183 | kWh | $0.05 |
Electricity Demand | $202,661 | 14,991 | kW-months/year | $13.52 |
Electricity Fees | $39,261 | - | $ | - |
Natural Gas | $95,187 | 19,079 | MMBtu | $4.99 |
TOTAL ENERGY COSTS | $636,930 | |||
RECOMMENDED SAVINGS* | $94,986 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $14,972 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $61,350 Cost: $196,482 |
$61,350 | 1,283,173 | - | - | - | - | - | - |
$61,350 1,283,173 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $14,182 Cost: $22,000 |
- | - | - | - | $14,182 | 2,843 | - | - |
- - kWh |
- - kW-months/year |
$14,182 2,843 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $6,742 Cost: - |
- | - | - | - | $6,742 | 1,351 | - | - |
- - kWh |
- - kW-months/year |
$6,742 1,351 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $4,335 Cost: - |
- | - | - | - | $4,335 | 869 | - | - |
- - kWh |
- - kW-months/year |
$4,335 869 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $3,420 Cost: $4,800 |
- | - | - | - | $3,420 | 686 | - | - |
- - kWh |
- - kW-months/year |
$3,420 686 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,531 Cost: $4,972 |
$1,531 | 32,016 | - | - | - | - | - | - |
$1,531 32,016 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,042 Cost: $2,808 |
$977 | 20,441 | $65 | 5 | - | - | - | - |
$977 20,441 kWh |
$65 5 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $867 Cost: $1,960 |
$867 | 17,170 | - | - | - | - | - | - |
$867 17,170 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $865 Cost: $625 |
$623 | 13,038 | $242 | 18 | - | - | - | - |
$623 13,038 kWh |
$242 18 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $455 Cost: $830 |
$220 | 4,599 | $85 | 6 | - | - | $150 | - |
$220 4,599 kWh |
$85 6 kW-months/year |
- - MMBtu |
$150 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.1131 REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC |
Savings: $197 Cost: $327 |
- | - | - | - | $197 | 39 | - | - |
- - kWh |
- - kW-months/year |
$197 39 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $94,986 Cost: $234,804 |
$65,568 | 1,370,437 | $392 | 29 | $28,876 | 5,788 | $150 | - | $65,568 1,370,437 kWh |
$392 29 kW-months/year |
$28,876 5,788 MMBtu |
$150 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $14,972 Cost: $10,570 |
$3,595 | 74,226 | $150 | 11 | $11,077 | 2,220 | $150 | - | $3,595 74,226 kWh |
$150 11 kW-months/year |
$11,077 2,220 MMBtu |
$150 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost |