Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center West Virginia University
Assessment Year 1996
Principal Product Insulation Products
NAICS n/a
SIC 3295 - Minerals, Ground Or Treated
Sales $10,000,000-$50,000,000
# of Employees 135
Plant Area (Sq.Ft.) 170,000
Annual Production 25,000,000 Pounds
Production Hrs. Annual 4,896
Location (State) PA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $105,859 2,523,740 kWh $0.04
Electricity Demand $25,357 6,517 kW-months/year $3.89
Electricity Fees $9,010 - $ -
Natural Gas $224,810 50,991 MMBtu $4.41
TOTAL ENERGY COSTS $365,036
RECOMMENDED SAVINGS* $46,918 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $16,376
#|Description Savings
Cost
Status Electricity Usage Natural Gas Solid Waste (non-haz) Administrative Changes Electricity Usage Natural Gas Solid Waste (non-haz) Administrative Changes
$ kWh $ MMBtu $ lb $ $
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$450
Cost:
$640
$450 12,603 - - - - - - $450
12,603
kWh
-
-
MMBtu
-
-
lb
-
-
$
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,654
Cost:
$42
$2,654 74,443 - - - - - - $2,654
74,443
kWh
-
-
MMBtu
-
-
lb
-
-
$
03: 2.1131 REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC Savings:
$14,094
Cost:
$8,910
- - $14,094 3,196 - - - - -
-
kWh
$14,094
3,196
MMBtu
-
-
lb
-
-
$
04: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$3,561
Cost:
$968
$(-86) (-2,345) $3,647 827 - - - - $(-86)
(-2,345)
kWh
$3,647
827
MMBtu
-
-
lb
-
-
$
05: 2.1213 DIRECT WARMEST AIR TO COMBUSTION INTAKE Savings:
$1,367
Cost:
$4,500
- - $1,367 310 - - - - -
-
kWh
$1,367
310
MMBtu
-
-
lb
-
-
$
06: 3.1163 USE PLASTIC PALLETS INSTEAD OF WOOD Savings:
$11,520
Cost:
$5,784
- - - - $11,520 - - - -
-
kWh
-
-
MMBtu
$11,520
-
lb
-
-
$
07: 3.1191 CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS Savings:
$13,272
Cost:
$7,000
- - - - - - $13,272 - -
-
kWh
-
-
MMBtu
-
-
lb
$13,272
-
$
TOTAL RECOMMENDED Savings:
$46,918
Cost:
$27,844
$3,018 84,701 $19,108 4,333 $11,520 - $13,272 - $3,018
84,701
kWh
$19,108
4,333
MMBtu
$11,520
-
lb
$13,272
-
$
TOTAL IMPLEMENTED Savings:
$16,376
Cost:
$7,682
$3,104 87,046 - - - - $13,272 - $3,104
87,046
kWh
-
-
MMBtu
-
-
lb
$13,272
-
$
Savings
Cost
$ kWh $ MMBtu $ lb $ $
Electricity Usage Natural Gas Solid Waste (non-haz) Administrative Changes Electricity Usage Natural Gas Solid Waste (non-haz) Administrative Changes