Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2001 |
Principal Product | Truck Bodies and Trailers |
NAICS | n/a |
SIC | 3713 - Truck And Bus Bodies |
Sales | $5,000,000-$10,000,000 |
# of Employees | 80 |
Plant Area (Sq.Ft.) | 116,800 |
Annual Production | 600 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $99,428 | 1,581,864 | kWh | $0.06 |
Natural Gas | $72,036 | 9,371 | MMBtu | $7.69 |
TOTAL ENERGY COSTS | $171,464 | |||
RECOMMENDED SAVINGS* | $100,540 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $83,334 |
#|Description |
Savings Cost |
Status | Electricity Usage | Natural Gas | Water Disposal | Administrative Changes | Electricity Usage | Natural Gas | Water Disposal | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $948 Cost: $300 |
$948 | 14,943 | - | - | - | - | - | - |
$948 14,943 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4157 ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM |
Savings: $776 Cost: $750 |
$776 | 21,975 | - | - | - | - | - | - |
$776 21,975 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,684 Cost: $4,400 |
$3,684 | 58,600 | - | - | - | - | - | - |
$3,684 58,600 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $3,599 Cost: $350 |
- | - | $3,599 | 468 | - | - | - | - |
- - kWh |
$3,599 468 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $1,215 Cost: $450 |
$1,215 | 19,338 | - | - | - | - | - | - |
$1,215 19,338 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $755 Cost: $400 |
$755 | 12,013 | - | - | - | - | - | - |
$755 12,013 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $861 Cost: $400 |
- | - | $861 | 112 | - | - | - | - |
- - kWh |
$861 112 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $6,323 Cost: $1,200 |
$6,323 | 100,499 | - | - | - | - | - | - |
$6,323 100,499 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7144 INSTALL SPECTRAL REFLECTORS / DELAMP |
Savings: $6,189 Cost: $11,368 |
$6,189 | 98,448 | - | - | - | - | - | - |
$6,189 98,448 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,118 Cost: $450 |
$2,118 | 33,695 | - | - | - | - | - | - |
$2,118 33,695 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,192 Cost: $100 |
$2,192 | 34,867 | - | - | - | - | - | - |
$2,192 34,867 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 3.4116 METER RECYCLED WATER (TO REDUCE SEWER CHARGES) |
Savings: $13,680 Cost: $220 |
- | - | - | - | $13,680 | - | - | - |
- - kWh |
- - MMBtu |
$13,680 - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 4.323 OPTIMIZE LOT SIZES TO REDUCE INVENTORY CARRYING COSTS |
Savings: $45,000 Cost: $15,000 |
- | - | - | - | - | - | $45,000 | - |
- - kWh |
- - MMBtu |
- - Tgal |
$45,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 4.731 ADVERTISE PRODUCT OR SERVICE |
Savings: $13,200 Cost: $2,000 |
- | - | - | - | - | - | $13,200 | - |
- - kWh |
- - MMBtu |
- - Tgal |
$13,200 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $100,540 Cost: $37,388 |
$24,200 | 394,378 | $4,460 | 580 | $13,680 | - | $58,200 | - | $24,200 394,378 kWh |
$4,460 580 MMBtu |
$13,680 - Tgal |
$58,200 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $83,334 Cost: $20,020 |
$11,454 | 191,622 | - | - | $13,680 | - | $58,200 | - | $11,454 191,622 kWh |
- - MMBtu |
$13,680 - Tgal |
$58,200 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Natural Gas | Water Disposal | Administrative Changes | Electricity Usage | Natural Gas | Water Disposal | Administrative Changes |