Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2002 |
Principal Product | Hydrogen Peroxide |
NAICS | n/a |
SIC | 2869 - Industrial Organic Chemicals, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 81 |
Plant Area (Sq.Ft.) | 54,600 |
Annual Production | 82,000,000 Pounds |
Production Hrs. Annual | 8,568 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,012,672 | 32,496,000 | kWh | $0.03 |
Natural Gas | $182,077 | 48,169 | MMBtu | $3.78 |
TOTAL ENERGY COSTS | $1,194,749 | |||
RECOMMENDED SAVINGS* | $231,667 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $124,940 |
#|Description |
Savings Cost |
Status | Electricity Usage | Coal | Water Disposal | Personnel Changes | Administrative Changes | Electricity Usage | Coal | Water Disposal | Personnel Changes | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | $ | Tgal | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $520 Cost: $150 |
$520 | 16,701 | - | - | - | - | - | - | - | - |
$520 16,701 kWh |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $38,997 Cost: $220 |
$39,657 | 1,253,258 | - | - | - | - | $(-660) | - | - | - |
$39,657 1,253,258 kWh |
- - MMBtu |
- - Tgal |
$(-660) - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6221 USE MOST EFFICIENT EQUIPMENT AT IT'S MAXIMUM CAPACITY AND LESS EFFICIENT EQUIPMENT ONLY WHEN NECESSARY |
Savings: $38,007 Cost: $550 |
$38,007 | 1,240,855 | - | - | - | - | - | - | - | - |
$38,007 1,240,855 kWh |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,642 Cost: $2,800 |
$1,642 | 48,996 | - | - | - | - | - | - | - | - |
$1,642 48,996 kWh |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $45,099 Cost: $1,050 |
- | - | $45,099 | 11,931 | - | - | - | - | - | - |
- - kWh |
$45,099 11,931 MMBtu |
- - Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $1,799 Cost: $1,500 |
$1,799 | 57,721 | - | - | - | - | - | - | - | - |
$1,799 57,721 kWh |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,317 Cost: $777 |
- | - | $2,317 | 613 | - | - | - | - | - | - |
- - kWh |
$2,317 613 MMBtu |
- - Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.4111 USE CLOSED CYCLE PROCESS TO MINIMIZE WASTE WATER PRODUCTION |
Savings: $8,000 Cost: $9,750 |
- | - | - | - | $8,000 | 4,000,000 | - | - | - | - |
- - kWh |
- - MMBtu |
$8,000 4,000,000 Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.4151 MINIMIZE WATER USAGE |
Savings: $8,228 Cost: $10,000 |
- | - | - | - | $8,228 | 514,285 | - | - | - | - |
- - kWh |
- - MMBtu |
$8,228 514,285 Tgal |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 4.422 UTILIZE OUTSIDE CONTRACTING |
Savings: $87,058 Cost: $1,100 |
- | - | - | - | - | - | - | - | $87,058 | - |
- - kWh |
- - MMBtu |
- - Tgal |
- - $ |
$87,058 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $231,667 Cost: $27,897 |
$81,625 | 2,617,531 | $47,416 | 12,544 | $16,228 | 4,514,285 | $(-660) | - | $87,058 | - | $81,625 2,617,531 kWh |
$47,416 12,544 MMBtu |
$16,228 4,514,285 Tgal |
$(-660) - $ |
$87,058 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $124,940 Cost: $2,747 |
$78,184 | 2,510,814 | $47,416 | 12,544 | - | - | $(-660) | - | - | - | $78,184 2,510,814 kWh |
$47,416 12,544 MMBtu |
- - Tgal |
$(-660) - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | MMBtu | $ | Tgal | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Coal | Water Disposal | Personnel Changes | Administrative Changes | Electricity Usage | Coal | Water Disposal | Personnel Changes | Administrative Changes |