IAC logo
IAC Assessment: WV0402
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: WV0402
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center West Virginia University
Assessment Year 2010
Principal Product Printed Materials
NAICS 323117 - Books Printing
SIC 2732 - Book Printing
Sales $50,000,000-$100,000,000
# of Employees 170
Plant Area (Sq.Ft.) 370,000
Annual Production 45,000,000 Units
Production Hrs. Annual 7,800
Location (State) WV
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $364,498 13,315,200 kWh $0.03
Electricity Demand $316,110 24,261 kW-months/year $13.03
Natural Gas $427,045 28,486 MMBtu $14.99
TOTAL ENERGY COSTS $1,107,653
RECOMMENDED SAVINGS* $157,129 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $35,224
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Personnel Changes Electricity Usage Electricity Demand Natural Gas Personnel Changes
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.2492 USE "HEAT WHEEL" OR OTHER HEAT EXCHANGER TO CROSS-EXCHANGE BUILDING EXHAUST AIR WITH MAKE-UP AIR Savings:
$63,671
Cost:
$114,000
$(-2,048) (-76,372) $(-1,509) (-117) $70,228 4,685 $(-3,000) - $(-2,048)
(-76,372)
kWh
$(-1,509)
(-117)
kW-months/year
$70,228
4,685
MMBtu
$(-3,000)
-
$
02: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$32,843
Cost:
$25,000
- - - - $32,843 2,191 - - -
-
kWh
-
-
kW-months/year
$32,843
2,191
MMBtu
-
-
$
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$16,488
Cost:
-
- - - - $17,658 1,178 $(-1,170) - -
-
kWh
-
-
kW-months/year
$17,658
1,178
MMBtu
$(-1,170)
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$15,346
Cost:
$9,200
$8,819 328,948 $6,527 506 - - - - $8,819
328,948
kWh
$6,527
506
kW-months/year
-
-
MMBtu
-
-
$
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$13,296
Cost:
$2,000
- - - - $13,296 887 - - -
-
kWh
-
-
kW-months/year
$13,296
887
MMBtu
-
-
$
06: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$12,095
Cost:
$4,000
$6,948 259,164 $5,147 399 - - - - $6,948
259,164
kWh
$5,147
399
kW-months/year
-
-
MMBtu
-
-
$
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$3,390
Cost:
-
$1,945 72,564 $1,445 112 - - - - $1,945
72,564
kWh
$1,445
112
kW-months/year
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$157,129
Cost:
$154,200
$15,664 584,304 $11,610 900 $134,025 8,941 $(-4,170) - $15,664
584,304
kWh
$11,610
900
kW-months/year
$134,025
8,941
MMBtu
$(-4,170)
-
$
TOTAL IMPLEMENTED Savings:
$35,224
Cost:
$9,200
$10,764 401,512 $7,972 618 $17,658 1,178 $(-1,170) - $10,764
401,512
kWh
$7,972
618
kW-months/year
$17,658
1,178
MMBtu
$(-1,170)
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $