Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2010 |
Principal Product | Printed Materials |
NAICS | 323117 - Books Printing |
SIC | 2732 - Book Printing |
Sales | $50,000,000-$100,000,000 |
# of Employees | 170 |
Plant Area (Sq.Ft.) | 370,000 |
Annual Production | 45,000,000 Units |
Production Hrs. Annual | 7,800 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $364,498 | 13,315,200 | kWh | $0.03 |
Electricity Demand | $316,110 | 24,261 | kW-months/year | $13.03 |
Natural Gas | $427,045 | 28,486 | MMBtu | $14.99 |
TOTAL ENERGY COSTS | $1,107,653 | |||
RECOMMENDED SAVINGS* | $157,129 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $35,224 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2492 USE "HEAT WHEEL" OR OTHER HEAT EXCHANGER TO CROSS-EXCHANGE BUILDING EXHAUST AIR WITH MAKE-UP AIR |
Savings: $63,671 Cost: $114,000 |
$(-2,048) | (-76,372) | $(-1,509) | (-117) | $70,228 | 4,685 | $(-3,000) | - |
$(-2,048) (-76,372) kWh |
$(-1,509) (-117) kW-months/year |
$70,228 4,685 MMBtu |
$(-3,000) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $32,843 Cost: $25,000 |
- | - | - | - | $32,843 | 2,191 | - | - |
- - kWh |
- - kW-months/year |
$32,843 2,191 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $16,488 Cost: - |
- | - | - | - | $17,658 | 1,178 | $(-1,170) | - |
- - kWh |
- - kW-months/year |
$17,658 1,178 MMBtu |
$(-1,170) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $15,346 Cost: $9,200 |
$8,819 | 328,948 | $6,527 | 506 | - | - | - | - |
$8,819 328,948 kWh |
$6,527 506 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $13,296 Cost: $2,000 |
- | - | - | - | $13,296 | 887 | - | - |
- - kWh |
- - kW-months/year |
$13,296 887 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $12,095 Cost: $4,000 |
$6,948 | 259,164 | $5,147 | 399 | - | - | - | - |
$6,948 259,164 kWh |
$5,147 399 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $3,390 Cost: - |
$1,945 | 72,564 | $1,445 | 112 | - | - | - | - |
$1,945 72,564 kWh |
$1,445 112 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $157,129 Cost: $154,200 |
$15,664 | 584,304 | $11,610 | 900 | $134,025 | 8,941 | $(-4,170) | - | $15,664 584,304 kWh |
$11,610 900 kW-months/year |
$134,025 8,941 MMBtu |
$(-4,170) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $35,224 Cost: $9,200 |
$10,764 | 401,512 | $7,972 | 618 | $17,658 | 1,178 | $(-1,170) | - | $10,764 401,512 kWh |
$7,972 618 kW-months/year |
$17,658 1,178 MMBtu |
$(-1,170) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes |