Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2013 |
Principal Product | Beer |
NAICS | 312120 - Breweries |
SIC | 2082 - Malt Beverages |
Sales | $50,000,000-$100,000,000 |
# of Employees | 205 |
Plant Area (Sq.Ft.) | 421,180 |
Annual Production | 30,000 Thousand Gallons |
Production Hrs. Annual | 6,000 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $604,930 | 15,862,285 | kWh | $0.04 |
Electricity Demand | $56,149 | 32,738 | kW-months/year | $1.72 |
Electricity Fees | $5,698 | - | $ | - |
Natural Gas | $656,768 | 135,876 | MMBtu | $4.83 |
TOTAL ENERGY COSTS | $1,323,545 | |||
RECOMMENDED SAVINGS* | $41,732 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,525 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $16,047 Cost: $31,578 |
$14,717 | 386,278 | $1,330 | 773 | - | - | - | - |
$14,717 386,278 kWh |
$1,330 773 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $6,907 Cost: $8,793 |
$6,334 | 166,255 | $573 | 333 | - | - | - | - |
$6,334 166,255 kWh |
$573 333 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $4,804 Cost: $1,700 |
- | - | - | - | $5,023 | 1,040 | $(-219) | - |
- - kWh |
- - kW-months/year |
$5,023 1,040 MMBtu |
$(-219) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4157 ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM |
Savings: $3,703 Cost: $1,000 |
$6,596 | 173,118 | $595 | 346 | - | - | $(-3,488) | - |
$6,596 173,118 kWh |
$595 346 kW-months/year |
- - MMBtu |
$(-3,488) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,539 Cost: $7,466 |
$3,247 | 85,220 | $292 | 170 | - | - | - | - |
$3,247 85,220 kWh |
$292 170 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,574 Cost: $3,281 |
- | - | - | - | $2,574 | 533 | - | - |
- - kWh |
- - kW-months/year |
$2,574 533 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $1,724 Cost: $617 |
- | - | - | - | $1,724 | 357 | - | - |
- - kWh |
- - kW-months/year |
$1,724 357 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $1,529 Cost: $3,263 |
$1,440 | 37,797 | $89 | 52 | - | - | - | - |
$1,440 37,797 kWh |
$89 52 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $497 Cost: $566 |
$618 | 16,230 | $55 | 32 | - | - | $(-176) | - |
$618 16,230 kWh |
$55 32 kW-months/year |
- - MMBtu |
$(-176) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $408 Cost: $29 |
$374 | 9,811 | $34 | 20 | - | - | - | - |
$374 9,811 kWh |
$34 20 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $41,732 Cost: $58,293 |
$33,326 | 874,709 | $2,968 | 1,726 | $9,321 | 1,930 | $(-3,883) | - | $33,326 874,709 kWh |
$2,968 1,726 kW-months/year |
$9,321 1,930 MMBtu |
$(-3,883) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,525 Cost: $14,042 |
$10,835 | 284,379 | $976 | 568 | $7,597 | 1,573 | $(-3,883) | - | $10,835 284,379 kWh |
$976 568 kW-months/year |
$7,597 1,573 MMBtu |
$(-3,883) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes |