Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center West Virginia University
Assessment Year 2018
Principal Product Waste Water Treatment
NAICS 221320 - Sewage Treatment Facilities
SIC 4952 - Sewerage Systems
Sales $10,000,000-$50,000,000
# of Employees 9
Plant Area (Sq.Ft.) 90,000
Annual Production 1,095,000 Units
Production Hrs. Annual 8,760
Location (State) OH
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $196,244 2,141,360 kWh $0.09
Electricity Demand $29,300 4,475 kW-months/year $6.55
Natural Gas $24,688 4,785 MMBtu $5.16
TOTAL ENERGY COSTS $340,232
RECOMMENDED SAVINGS* $152,776 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $103,786
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Personnel Changes Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Personnel Changes
$ kWh $ kW-months/year $ MMBtu $ lb $ $
01: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS Savings:
$84,000
Cost:
$3,000
- - - - - - $90,000 6,000,000 $(-6,000) - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$90,000
6,000,000
lb
$(-6,000)
-
$
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$45,746
Cost:
$111,500
$41,665 454,856 $4,081 623 - - - - - - $41,665
454,856
kWh
$4,081
623
kW-months/year
-
-
MMBtu
-
-
lb
-
-
$
03: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$6,517
Cost:
$3,640
$5,620 61,353 $897 137 - - - - - - $5,620
61,353
kWh
$897
137
kW-months/year
-
-
MMBtu
-
-
lb
-
-
$
04: 2.4313 PROVIDE PROPER MAINTENANCE OF MOTOR DRIVEN EQUIPMENT Savings:
$4,668
Cost:
$19,300
$4,249 46,390 $419 64 - - - - - - $4,249
46,390
kWh
$419
64
kW-months/year
-
-
MMBtu
-
-
lb
-
-
$
05: 2.4157 ESTABLISH A PREDICTIVE MAINTENANCE PROGRAM Savings:
$4,560
Cost:
$1,000
$4,154 45,348 $406 62 - - - - - - $4,154
45,348
kWh
$406
62
kW-months/year
-
-
MMBtu
-
-
lb
-
-
$
06: 2.7264 INTERLOCK HEATING AND AIR CONDITIONING SYSTEMS TO PREVENT SIMULTANEOUS OPERATION Savings:
$2,563
Cost:
$11,400
$1,348 14,717 $131 20 $1,084 210 - - - - $1,348
14,717
kWh
$131
20
kW-months/year
$1,084
210
MMBtu
-
-
lb
-
-
$
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,998
Cost:
$7,133
$1,670 18,228 $328 50 - - - - - - $1,670
18,228
kWh
$328
50
kW-months/year
-
-
MMBtu
-
-
lb
-
-
$
08: 2.4151 DEVELOP A REPAIR/REPLACE POLICY Savings:
$2,043
Cost:
$721
$1,860 20,305 $183 28 - - - - - - $1,860
20,305
kWh
$183
28
kW-months/year
-
-
MMBtu
-
-
lb
-
-
$
09: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$681
Cost:
$3,000
- - - - $681 132 - - - - -
-
kWh
-
-
kW-months/year
$681
132
MMBtu
-
-
lb
-
-
$
TOTAL RECOMMENDED Savings:
$152,776
Cost:
$160,694
$60,566 661,197 $6,445 984 $1,765 342 $90,000 6,000,000 $(-6,000) - $60,566
661,197
kWh
$6,445
984
kW-months/year
$1,765
342
MMBtu
$90,000
6,000,000
lb
$(-6,000)
-
$
TOTAL IMPLEMENTED Savings:
$103,786
Cost:
$34,794
$17,553 191,624 $2,233 341 - - $90,000 6,000,000 $(-6,000) - $17,553
191,624
kWh
$2,233
341
kW-months/year
-
-
MMBtu
$90,000
6,000,000
lb
$(-6,000)
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ lb $ $
Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Personnel Changes Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Personnel Changes