Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2021 |
Principal Product | Fabricated Metal Products |
NAICS | 332312 - Fabricated Structural Metal Manufacturing |
SIC | 3441 - Fabricated Structural Metal |
Sales | $10,000,000-$50,000,000 |
# of Employees | 80 |
Plant Area (Sq.Ft.) | 55,000 |
Annual Production | 4,000 Tons |
Production Hrs. Annual | 3,978 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $42,220 | 1,159,718 | kWh | $0.04 |
Electricity Demand | $54,283 | 3,247 | kW-months/year | $16.72 |
Electricity Fees | $5,203 | - | $ | - |
Natural Gas | $3,952 | 517 | MMBtu | $7.64 |
TOTAL ENERGY COSTS | $105,658 | |||
RECOMMENDED SAVINGS* | $25,928 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $2,480 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $14,736 Cost: $14,181 |
$8,830 | 242,587 | $5,906 | 353 | - | - | - | - | - | - |
$8,830 242,587 kWh |
$5,906 353 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,236 Cost: $13,076 |
$1,942 | 53,359 | $3,294 | 197 | - | - | - | - | - | - |
$1,942 53,359 kWh |
$3,294 197 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $3,155 Cost: $2,492 |
- | - | - | - | - | - | $3,155 | 413 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,155 413 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,519 Cost: $50 |
$934 | 25,669 | $585 | 35 | - | - | - | - | - | - |
$934 25,669 kWh |
$585 35 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $635 Cost: $1,054 |
$635 | 17,446 | - | - | - | - | - | - | - | - |
$635 17,446 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $326 Cost: $358 |
$308 | 8,451 | $418 | 25 | - | - | - | - | $(-400) | - |
$308 8,451 kWh |
$418 25 kW-months/year |
- - $ |
- - MMBtu |
$(-400) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $321 Cost: $1,410 |
- | - | - | - | $321 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$321 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $25,928 Cost: $32,621 |
$12,649 | 347,512 | $10,203 | 610 | $321 | - | $3,155 | 413 | $(-400) | - | $12,649 347,512 kWh |
$10,203 610 kW-months/year |
$321 - $ |
$3,155 413 MMBtu |
$(-400) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $2,480 Cost: $1,462 |
$1,877 | 51,566 | $1,003 | 60 | - | - | - | - | $(-400) | - | $1,877 51,566 kWh |
$1,003 60 kW-months/year |
- - $ |
- - MMBtu |
$(-400) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes |