Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Arkansas |
---|---|
Assessment Year | 1996 |
Principal Product | Table and Floor Lamps |
NAICS | n/a |
SIC | 3645 - Residential Lighting Fixtures |
Sales | $50,000,000-$100,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 245,000 |
Annual Production | 8,000,000 Pieces |
Production Hrs. Annual | 2,738 |
Location (State) | AR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $56,944 | 991,208 | kWh | $0.06 |
Electricity Demand | $37,091 | 4,130 | kW-months/year | $8.98 |
Natural Gas | $12,614 | 2,345 | MMBtu | $5.38 |
TOTAL ENERGY COSTS | $170,773 | |||
RECOMMENDED SAVINGS* | $95,020 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $40,228 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $5,317 Cost: $720 |
$2,852 | 50,996 | $2,465 | 141 | - | - | - | - |
$2,852 50,996 kWh |
$2,465 141 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,355 Cost: $1,976 |
$2,479 | 44,256 | $1,876 | 194 | - | - | - | - |
$2,479 44,256 kWh |
$1,876 194 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,725 Cost: $140 |
$983 | 17,585 | $742 | 77 | - | - | - | - |
$983 17,585 kWh |
$742 77 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $549 Cost: $100 |
$317 | 5,569 | $232 | 24 | - | - | - | - |
$317 5,569 kWh |
$232 24 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $6,633 Cost: $100 |
- | - | - | - | $6,633 | 863 | - | - |
- - kWh |
- - kW-months/year |
$6,633 863 MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $709 Cost: $1,830 |
$141 | 2,638 | $568 | 59 | - | - | - | - |
$141 2,638 kWh |
$568 59 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $119 Cost: - |
$57 | 1,172 | $62 | 6 | - | - | - | - |
$57 1,172 kWh |
$62 6 kW-months/year |
- - MMBtu |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.5315 LEASE / PURCHASE BALER; SELL CARDBOARD TO RECYCLER |
Savings: $27,454 Cost: $1,488 |
- | - | - | - | - | - | $27,454 | 1,488,000 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$27,454 1,488,000 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.1162 USE LESS WASTEFUL PACKAGING |
Savings: $48,159 Cost: - |
- | - | - | - | - | - | $48,159 | 796,000 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$48,159 796,000 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $95,020 Cost: $6,354 |
$6,829 | 122,216 | $5,945 | 501 | $6,633 | 863 | $75,613 | 2,284,000 | $6,829 122,216 kWh |
$5,945 501 kW-months/year |
$6,633 863 MMBtu |
$75,613 2,284,000 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $40,228 Cost: $6,254 |
$6,829 | 122,216 | $5,945 | 501 | - | - | $27,454 | 1,488,000 | $6,829 122,216 kWh |
$5,945 501 kW-months/year |
- - MMBtu |
$27,454 1,488,000 lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) |