Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Arkansas |
---|---|
Assessment Year | 1997 |
Principal Product | Air Filtration Media |
NAICS | n/a |
SIC | 3564 - Blowers And Fans |
Sales | $10,000,000-$50,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 88,957 |
Annual Production | 88,000,000 Thousand Feet |
Production Hrs. Annual | 7,200 |
Location (State) | AR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $219,934 | 6,675,850 | kWh | $0.03 |
Electricity Demand | $65,760 | 11,624 | kW-months/year | $5.66 |
Natural Gas | $282,814 | 106,872 | MMBtu | $2.65 |
TOTAL ENERGY COSTS | $737,717 | |||
RECOMMENDED SAVINGS* | $84,781 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $10,508 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Disposal | Solid Waste (non-haz) | Primary Product | Electricity Usage | Electricity Demand | Water Disposal | Solid Waste (non-haz) | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | $ | lb | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $2,654 Cost: $690 |
$2,042 | 61,841 | $612 | 108 | - | - | - | - | - | - |
$2,042 61,841 kWh |
$612 108 kW-months/year |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,804 Cost: $1,415 |
$2,128 | 64,478 | $676 | 119 | - | - | - | - | - | - |
$2,128 64,478 kWh |
$676 119 kW-months/year |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $856 Cost: - |
$583 | 17,585 | $273 | 48 | - | - | - | - | - | - |
$583 17,585 kWh |
$273 48 kW-months/year |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,478 Cost: $600 |
$1,927 | 58,324 | $551 | 97 | - | - | - | - | - | - |
$1,927 58,324 kWh |
$551 97 kW-months/year |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,578 Cost: $350 |
$2,783 | 83,822 | $795 | 141 | - | - | - | - | - | - |
$2,783 83,822 kWh |
$795 141 kW-months/year |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $10,942 Cost: $17,710 |
$8,131 | 246,190 | $2,811 | 497 | - | - | - | - | - | - |
$8,131 246,190 kWh |
$2,811 497 kW-months/year |
- - Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.5315 LEASE / PURCHASE BALER; SELL CARDBOARD TO RECYCLER |
Savings: $853 Cost: - |
- | - | - | - | - | - | $853 | 18,480 | - | - |
- - kWh |
- - kW-months/year |
- - Tgal |
$853 18,480 lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.4151 MINIMIZE WATER USAGE |
Savings: $616 Cost: $100 |
- | - | - | - | $616 | 181,300 | - | - | - | - |
- - kWh |
- - kW-months/year |
$616 181,300 Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.651 INSTALL BACK-UP EQUIPMENT |
Savings: $60,000 Cost: $54,000 |
- | - | - | - | - | - | - | - | $60,000 | - |
- - kWh |
- - kW-months/year |
- - Tgal |
- - lb |
$60,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $84,781 Cost: $74,865 |
$17,594 | 532,240 | $5,718 | 1,010 | $616 | 181,300 | $853 | 18,480 | $60,000 | - | $17,594 532,240 kWh |
$5,718 1,010 kW-months/year |
$616 181,300 Tgal |
$853 18,480 lb |
$60,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $10,508 Cost: $2,555 |
$7,536 | 227,726 | $2,356 | 416 | $616 | 181,300 | - | - | - | - | $7,536 227,726 kWh |
$2,356 416 kW-months/year |
$616 181,300 Tgal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | $ | lb | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Disposal | Solid Waste (non-haz) | Primary Product | Electricity Usage | Electricity Demand | Water Disposal | Solid Waste (non-haz) | Primary Product |