Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Arizona State University
Assessment Year 1996
Principal Product Custom Semiconductors
NAICS n/a
SIC 3674 - Semiconductors And Related Devices
Sales $50,000,000-$100,000,000
# of Employees 200
Plant Area (Sq.Ft.) 72,740
Annual Production 230,000 Pieces
Production Hrs. Annual 8,568
Location (State) AZ
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $496,982 8,512,310 kWh $0.06
Electricity Demand $41,566 14,772 kW-months/year $2.81
TOTAL ENERGY COSTS $554,456
RECOMMENDED SAVINGS* $37,502 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $17,672
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Water Disposal Electricity Usage Electricity Demand Water Disposal
$ kWh $ kW-months/year $ Tgal
01: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$14,536
Cost:
$7,000
$14,536 249,121 - - - - $14,536
249,121
kWh
-
-
kW-months/year
-
-
Tgal
02: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$2,116
Cost:
$3,200
$2,116 36,342 - - - - $2,116
36,342
kWh
-
-
kW-months/year
-
-
Tgal
03: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$4,440
Cost:
$20,000
$4,440 76,202 - - - - $4,440
76,202
kWh
-
-
kW-months/year
-
-
Tgal
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$3,906
Cost:
$2,211
$3,653 62,427 $253 90 - - $3,653
62,427
kWh
$253
90
kW-months/year
-
-
Tgal
05: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,348
Cost:
-
$1,257 21,688 $91 32 - - $1,257
21,688
kWh
$91
32
kW-months/year
-
-
Tgal
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,288
Cost:
-
$1,288 21,981 - - - - $1,288
21,981
kWh
-
-
kW-months/year
-
-
Tgal
07: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,105
Cost:
$1,200
$2,105 36,049 - - - - $2,105
36,049
kWh
-
-
kW-months/year
-
-
Tgal
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$5,873
Cost:
$11,962
$5,252 89,977 $621 221 - - $5,252
89,977
kWh
$621
221
kW-months/year
-
-
Tgal
09: 3.4151 MINIMIZE WATER USAGE Savings:
$1,890
Cost:
$491
- - - - $1,890 1,023,422 -
-
kWh
-
-
kW-months/year
$1,890
1,023,422
Tgal
TOTAL RECOMMENDED Savings:
$37,502
Cost:
$46,064
$34,647 593,787 $965 343 $1,890 1,023,422 $34,647
593,787
kWh
$965
343
kW-months/year
$1,890
1,023,422
Tgal
TOTAL IMPLEMENTED Savings:
$17,672
Cost:
$35,373
$16,707 286,343 $965 343 - - $16,707
286,343
kWh
$965
343
kW-months/year
-
-
Tgal
Savings
Cost
$ kWh $ kW-months/year $ Tgal
Electricity Usage Electricity Demand Water Disposal Electricity Usage Electricity Demand Water Disposal