Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 1996 |
Principal Product | Custom Semiconductors |
NAICS | n/a |
SIC | 3674 - Semiconductors And Related Devices |
Sales | $10,000,000-$50,000,000 |
# of Employees | 550 |
Plant Area (Sq.Ft.) | 146,735 |
Annual Production | 35,000 Pieces |
Production Hrs. Annual | 8,400 |
Location (State) | AZ |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $983,135 | 24,217,468 | kWh | $0.04 |
Electricity Demand | $395,316 | 36,835 | kW-months/year | $10.73 |
Natural Gas | $197,959 | 51,371 | MMBtu | $3.85 |
TOTAL ENERGY COSTS | $1,675,423 | |||
RECOMMENDED SAVINGS* | $117,351 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $89,441 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $9,415 Cost: $7,000 |
$4,210 | 113,716 | $5,205 | 496 | - | - | - | - | - | - |
$4,210 113,716 kWh |
$5,205 496 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $4,108 Cost: $1,750 |
$3,457 | 53,048 | $651 | 232 | - | - | - | - | - | - |
$3,457 53,048 kWh |
$651 232 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $1,233 Cost: $2,880 |
$1,233 | 19,050 | - | - | - | - | - | - | - | - |
$1,233 19,050 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $21,398 Cost: $25,000 |
$13,965 | 371,336 | $7,433 | 709 | - | - | - | - | - | - |
$13,965 371,336 kWh |
$7,433 709 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $15,892 Cost: $35,000 |
$10,700 | 255,276 | $5,192 | 495 | - | - | - | - | - | - |
$10,700 255,276 kWh |
$5,192 495 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $10,968 Cost: $6,000 |
$10,968 | 283,705 | - | - | - | - | - | - | - | - |
$10,968 283,705 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $2,569 Cost: $1,500 |
$2,569 | 39,566 | - | - | - | - | - | - | - | - |
$2,569 39,566 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $5,954 Cost: $4,163 |
$3,944 | 104,924 | $2,010 | 192 | - | - | - | - | - | - |
$3,944 104,924 kWh |
$2,010 192 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $315 Cost: - |
$315 | 8,499 | - | - | - | - | - | - | - | - |
$315 8,499 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $3,519 Cost: $2,240 |
$2,405 | 90,563 | $1,114 | 106 | - | - | - | - | - | - |
$2,405 90,563 kWh |
$1,114 106 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $27,847 Cost: $54,958 |
$20,408 | 544,256 | $7,439 | 709 | - | - | - | - | - | - |
$20,408 544,256 kWh |
$7,439 709 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $207 Cost: $800 |
$153 | 3,517 | $54 | 5 | - | - | - | - | - | - |
$153 3,517 kWh |
$54 5 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $3,057 Cost: $2,475 |
$3,057 | 75,615 | - | - | - | - | - | - | - | - |
$3,057 75,615 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $4,827 Cost: $1,200 |
- | - | - | - | $4,827 | 1,253 | - | - | - | - |
- - kWh |
- - kW-months/year |
$4,827 1,253 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
15: 3.4113 TREAT AND REUSE RINSE WATERS |
Savings: $6,042 Cost: $22,500 |
- | - | - | - | - | - | $11,542 | 3,136,500 | $(-5,500) | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$11,542 3,136,500 Tgal |
$(-5,500) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $117,351 Cost: $167,466 |
$77,384 | 1,963,071 | $29,098 | 2,944 | $4,827 | 1,253 | $11,542 | 3,136,500 | $(-5,500) | - | $77,384 1,963,071 kWh |
$29,098 2,944 kW-months/year |
$4,827 1,253 MMBtu |
$11,542 3,136,500 Tgal |
$(-5,500) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $89,441 Cost: $129,071 |
$56,684 | 1,442,556 | $27,930 | 2,833 | $4,827 | 1,253 | - | - | - | - | $56,684 1,442,556 kWh |
$27,930 2,833 kW-months/year |
$4,827 1,253 MMBtu |
- - Tgal |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Ancillary Material Cost |