Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 1996 |
Principal Product | Potato and Corn Chip Snacks |
NAICS | n/a |
SIC | 2096 - Potato Chips And Similar Snacks |
Sales | $100,000,000-$500,000,000 |
# of Employees | 300 |
Plant Area (Sq.Ft.) | 180,000 |
Annual Production | 25,000 Tons |
Production Hrs. Annual | 7,488 |
Location (State) | AZ |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $529,187 | 8,423,798 | kWh | $0.06 |
Electricity Demand | $27,454 | 14,070 | kW-months/year | $1.95 |
TOTAL ENERGY COSTS | $844,814 | |||
RECOMMENDED SAVINGS* | $36,289 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $16,882 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Disposal | Electricity Usage | Electricity Demand | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $7,388 Cost: $10,000 |
$6,879 | 145,955 | $509 | 275 | - | - |
$6,879 145,955 kWh |
$509 275 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $8,466 Cost: $4,200 |
$7,229 | 153,283 | $1,237 | 669 | - | - |
$7,229 153,283 kWh |
$1,237 669 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $932 Cost: $2,080 |
$932 | 19,930 | - | - | - | - |
$932 19,930 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $119 Cost: $115 |
$113 | 2,345 | $6 | 3 | - | - |
$113 2,345 kWh |
$6 3 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $8,795 Cost: $6,778 |
$8,228 | 174,678 | $567 | 306 | - | - |
$8,228 174,678 kWh |
$567 306 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $2,455 Cost: $3,500 |
$3,234 | 80,305 | $407 | 220 | $(-1,186) | (-727,834) |
$3,234 80,305 kWh |
$407 220 kW-months/year |
$(-1,186) (-727,834) Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $283 Cost: - |
$266 | 5,569 | $17 | 9 | - | - |
$266 5,569 kWh |
$17 9 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $1,148 Cost: $5,730 |
$1,010 | 21,395 | $138 | 74 | - | - |
$1,010 21,395 kWh |
$138 74 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,607 Cost: $26,161 |
$6,090 | 129,250 | $517 | 280 | - | - |
$6,090 129,250 kWh |
$517 280 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.4154 ELIMINATE LEAKS IN WATER LINES AND VALVES |
Savings: $96 Cost: $100 |
- | - | - | - | $96 | 58,752 |
- - kWh |
- - kW-months/year |
$96 58,752 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $36,289 Cost: $58,664 |
$33,981 | 732,710 | $3,398 | 1,836 | $(-1,090) | (-669,082) | $33,981 732,710 kWh |
$3,398 1,836 kW-months/year |
$(-1,090) (-669,082) Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $16,882 Cost: $16,380 |
$15,040 | 319,168 | $1,746 | 944 | $96 | 58,752 | $15,040 319,168 kWh |
$1,746 944 kW-months/year |
$96 58,752 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Disposal | Electricity Usage | Electricity Demand | Water Disposal |