Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 1996 |
Principal Product | Brass Door Locks |
NAICS | n/a |
SIC | 3429 - Hardware, Nec |
Sales | $100,000,000-$500,000,000 |
# of Employees | 475 |
Plant Area (Sq.Ft.) | 238,000 |
Annual Production | 9,000,000 Pieces |
Production Hrs. Annual | 5,700 |
Location (State) | AZ |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $779,895 | 11,136,284 | kWh | $0.07 |
Electricity Demand | $173,102 | 22,860 | kW-months/year | $7.57 |
TOTAL ENERGY COSTS | $1,197,609 | |||
RECOMMENDED SAVINGS* | $112,753 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $108,849 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Disposal | Electricity Usage | Electricity Demand | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $34,527 Cost: $45,000 |
$26,214 | 374,560 | $11,582 | 1,577 | $(-3,269) | (-923,400) |
$26,214 374,560 kWh |
$11,582 1,577 kW-months/year |
$(-3,269) (-923,400) Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $5,963 Cost: $7,000 |
$3,196 | 58,910 | $2,767 | 377 | - | - |
$3,196 58,910 kWh |
$2,767 377 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $24,827 Cost: $17,598 |
$20,143 | 287,808 | $4,684 | 638 | - | - |
$20,143 287,808 kWh |
$4,684 638 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $8,838 Cost: - |
$7,239 | 103,458 | $1,599 | 218 | - | - |
$7,239 103,458 kWh |
$1,599 218 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $9,599 Cost: $25,001 |
$9,365 | 111,958 | $234 | 32 | - | - |
$9,365 111,958 kWh |
$234 32 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,904 Cost: $6,140 |
$3,198 | 45,721 | $706 | 96 | - | - |
$3,198 45,721 kWh |
$706 96 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $881 Cost: $450 |
$881 | 12,603 | - | - | - | - |
$881 12,603 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.1222 REDUCE WATER USE WITH COUNTER CURRENT RINSING |
Savings: $24,214 Cost: $900 |
- | - | - | - | $24,214 | 6,840,000 |
- - kWh |
- - kW-months/year |
$24,214 6,840,000 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $112,753 Cost: $102,089 |
$70,236 | 995,018 | $21,572 | 2,938 | $20,945 | 5,916,600 | $70,236 995,018 kWh |
$21,572 2,938 kW-months/year |
$20,945 5,916,600 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $108,849 Cost: $95,949 |
$67,038 | 949,297 | $20,866 | 2,842 | $20,945 | 5,916,600 | $67,038 949,297 kWh |
$20,866 2,842 kW-months/year |
$20,945 5,916,600 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Disposal | Electricity Usage | Electricity Demand | Water Disposal |