Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Arizona State University |
---|---|
Assessment Year | 2003 |
Principal Product | Wallboard, Plaster |
NAICS | 327420 - Gypsum Product Manufacturing |
SIC | 3275 - Gypsum Products |
Sales | $50,000,000-$100,000,000 |
# of Employees | 110 |
Plant Area (Sq.Ft.) | 600,000 |
Annual Production | 218,124 Thousand Feet |
Production Hrs. Annual | 8,760 |
Location (State) | NV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,976,152 | 31,300,918 | kWh | $0.06 |
Electricity Demand | $169,642 | 72,871 | kW-months/year | $2.33 |
Electricity Fees | $535,231 | - | $ | - |
Natural Gas | $9,390,449 | 2,475,345 | MMBtu | $3.79 |
TOTAL ENERGY COSTS | $12,071,474 | |||
RECOMMENDED SAVINGS* | $1,075,962 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $6,985 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7145 INSTALL SKYLIGHTS |
Savings: $552 Cost: $22,526 |
$552 | 195,216 | - | - | - | - |
$552 195,216 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $265 Cost: $2,353 |
$141 | 18,757 | $124 | 25 | - | - |
$141 18,757 kWh |
$124 25 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,751 Cost: $10,939 |
$900 | 52,201 | $851 | 195 | - | - |
$900 52,201 kWh |
$851 195 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $6,720 Cost: $750 |
$6,720 | 6,026 | - | - | - | - |
$6,720 6,026 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $17,401 Cost: $10,050 |
$16,801 | 141,391 | $600 | 125 | - | - |
$16,801 141,391 kWh |
$600 125 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $1,049,273 Cost: $2,100,000 |
$1,555,500 | 25,500,000 | $255,367 | 52,871 | $(-761,594) | (-201,480) |
$1,555,500 25,500,000 kWh |
$255,367 52,871 kW-months/year |
$(-761,594) (-201,480) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,075,962 Cost: $2,146,618 |
$1,580,614 | 25,913,591 | $256,942 | 53,216 | $(-761,594) | (-201,480) | $1,580,614 25,913,591 kWh |
$256,942 53,216 kW-months/year |
$(-761,594) (-201,480) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $6,985 Cost: $3,103 |
$6,861 | 24,783 | $124 | 25 | - | - | $6,861 24,783 kWh |
$124 25 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |