IAC logo
IAC Assessment: AS0387
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: AS0387
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Arizona State University
Assessment Year 2004
Principal Product Newspapers
NAICS 511110 - Newspaper Publishers
SIC 2711 - Newspapers
Sales $50,000,000-$100,000,000
# of Employees 500
Plant Area (Sq.Ft.) 100,000
Annual Production 12,000 Tons
Production Hrs. Annual 8,760
Location (State) AZ
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $248,490 4,939,049 kWh $0.05
Electricity Demand $41,290 11,986 kW-months/year $3.44
Electricity Fees $23,438 - $ -
TOTAL ENERGY COSTS $313,218
RECOMMENDED SAVINGS* $25,499 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $5,155
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$4,518
Cost:
$500
$4,116 75,966 $402 104 $4,116
75,966
kWh
$402
104
kW-months/year
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$1,736
Cost:
$60
$830 20,250 $906 108 $830
20,250
kWh
$906
108
kW-months/year
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$4,601
Cost:
$14,813
$4,192 77,368 $409 106 $4,192
77,368
kWh
$409
106
kW-months/year
04: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$309
Cost:
$675
$309 5,694 - - $309
5,694
kWh
-
-
kW-months/year
05: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$2,451
Cost:
$2,911
$2,228 42,225 $223 58 $2,228
42,225
kWh
$223
58
kW-months/year
06: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$9,180
Cost:
$10,083
$8,619 159,082 $561 218 $8,619
159,082
kWh
$561
218
kW-months/year
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,704
Cost:
$60
$2,464 45,493 $240 62 $2,464
45,493
kWh
$240
62
kW-months/year
TOTAL RECOMMENDED Savings:
$25,499
Cost:
$29,102
$22,758 426,078 $2,741 656 $22,758
426,078
kWh
$2,741
656
kW-months/year
TOTAL IMPLEMENTED Savings:
$5,155
Cost:
$2,971
$4,692 87,718 $463 120 $4,692
87,718
kWh
$463
120
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand