Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Arizona State University
Assessment Year 2020
Principal Product Treated Surface Water
NAICS 221310 - Water Supply and Irrigation Systems
SIC 4941 - Water Supply
Sales <$500,000
# of Employees 50
Plant Area (Sq.Ft.) 76,000
Annual Production 2,900,000 Thousand Gallons
Production Hrs. Annual 7,320
Location (State) AZ
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $433,417 7,194,567 kWh $0.06
Electricity Demand $237,609 18,514 kW-months/year $12.83
Electricity Fees $53,943 - $ -
TOTAL ENERGY COSTS $724,969
RECOMMENDED SAVINGS* $25,517 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $8,102
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Administrative Changes Electricity Usage Electricity Demand Administrative Changes
$ kWh $ kW-months/year $ $
01: 2.3137 USE POWER DURING OFF-PEAK PERIODS Savings:
$7,396
Cost:
$298
- - - - $7,396 - -
-
kWh
-
-
kW-months/year
$7,396
-
$
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$7,249
Cost:
$1,100
$5,671 94,516 $1,578 123 - - $5,671
94,516
kWh
$1,578
123
kW-months/year
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$5,880
Cost:
$2,996
$4,592 76,538 $1,288 100 - - $4,592
76,538
kWh
$1,288
100
kW-months/year
-
-
$
04: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL Savings:
$3,159
Cost:
$9,000
$2,466 41,104 $693 54 - - $2,466
41,104
kWh
$693
54
kW-months/year
-
-
$
05: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,068
Cost:
$540
$1,068 17,828 - - - - $1,068
17,828
kWh
-
-
kW-months/year
-
-
$
06: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$706
Cost:
$912
$553 9,232 $153 12 - - $553
9,232
kWh
$153
12
kW-months/year
-
-
$
07: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$59
Cost:
$113
$46 769 $13 1 - - $46
769
kWh
$13
1
kW-months/year
-
-
$
TOTAL RECOMMENDED Savings:
$25,517
Cost:
$14,959
$14,396 239,987 $3,725 290 $7,396 - $14,396
239,987
kWh
$3,725
290
kW-months/year
$7,396
-
$
TOTAL IMPLEMENTED Savings:
$8,102
Cost:
$1,210
$553 9,232 $153 12 $7,396 - $553
9,232
kWh
$153
12
kW-months/year
$7,396
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand Administrative Changes Electricity Usage Electricity Demand Administrative Changes