Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Bradley University
Assessment Year 2006
Principal Product Scrap Metal, Wood, and Paper Recycling
NAICS 331314 - Secondary Smelting and Alloying of Aluminum
SIC 3341 - Secondary Nonferrous Metals
Sales $10,000,000-$50,000,000
# of Employees 59
Plant Area (Sq.Ft.) 60,000
Annual Production 100,000 Tons
Production Hrs. Annual 2,730
Location (State) IL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $31,474 468,731 kWh $0.07
Electricity Demand $1,134 3,196 kW-months/year $0.35
Natural Gas $25,295 2,780 MMBtu $9.10
TOTAL ENERGY COSTS $79,023
RECOMMENDED SAVINGS* $6,225 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Natural Gas Personnel Changes Ancillary Material Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,732
Cost:
$3,640
$2,639 39,312 $60 173 - - $7 - $26 - $2,639
39,312
kWh
$60
173
kW-months/year
-
-
MMBtu
$7
-
$
$26
-
$
02: 2.7231 USE RADIANT HEATER FOR SPOT HEATING Savings:
$1,386
Cost:
$3,200
$73 1,220 $1 5 $1,312 144 - - - - $73
1,220
kWh
$1
5
kW-months/year
$1,312
144
MMBtu
-
-
$
-
-
$
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$483
Cost:
$105
- - - - $483 53 - - - - -
-
kWh
-
-
kW-months/year
$483
53
MMBtu
-
-
$
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$485
Cost:
$143
$282 4,204 $6 18 - - $40 - $157 - $282
4,204
kWh
$6
18
kW-months/year
-
-
MMBtu
$40
-
$
$157
-
$
05: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$482
Cost:
$220
$468 6,974 $14 39 - - - - - - $468
6,974
kWh
$14
39
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
06: 2.2515 USE OPTIMUM THICKNESS INSULATION Savings:
$432
Cost:
$210
- - - - $432 48 - - - - -
-
kWh
-
-
kW-months/year
$432
48
MMBtu
-
-
$
-
-
$
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$225
Cost:
$60
$220 3,275 $5 14 - - - - - - $220
3,275
kWh
$5
14
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$6,225
Cost:
$7,578
$3,682 54,985 $86 249 $2,227 245 $47 - $183 - $3,682
54,985
kWh
$86
249
kW-months/year
$2,227
245
MMBtu
$47
-
$
$183
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $