Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of North Carolina, Charlotte
Assessment Year 2024
Principal Product Home Heating Pellets, Industrial Wood Flour, Animal Bedding
NAICS 321219 - Reconstituted Wood Product Manufacturing
SIC 2493 - Reconstituted Wood Products
Sales $10,000,000-$50,000,000
# of Employees 45
Plant Area (Sq.Ft.) 85,800
Annual Production 80,000 Tons
Production Hrs. Annual 7,488
Location (State) VA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,445,659 13,345,500 kWh $0.11
Electricity Fees $12,714 - $ -
Natural Gas $15,961 1,848 MMBtu $8.64
TOTAL ENERGY COSTS $1,474,334
RECOMMENDED SAVINGS* $155,384 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$46,974
Cost:
$309,771
$46,974 434,943 - - $46,974
434,943
kWh
-
-
MMBtu
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$22,612
Cost:
$12,962
$22,612 209,373 - - $22,612
209,373
kWh
-
-
MMBtu
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$351
Cost:
$1,191
$351 3,250 - - $351
3,250
kWh
-
-
MMBtu
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,953
Cost:
$3,987
$3,953 36,598 - - $3,953
36,598
kWh
-
-
MMBtu
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$3,480
Cost:
$10,000
$(-596) (-5,521) $4,077 472 $(-596)
(-5,521)
kWh
$4,077
472
MMBtu
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$3,222
Cost:
$10,000
$3,222 29,830 - - $3,222
29,830
kWh
-
-
MMBtu
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$74,792
Cost:
$250,000
$74,792 692,521 - - $74,792
692,521
kWh
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$155,384
Cost:
$597,911
$151,307 1,400,994 $4,077 472 $151,307
1,400,994
kWh
$4,077
472
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas