IAC Center Clemson University
Assessment Year 2019
Principal Product Liquid Flow Meters - Coriolis
NAICS 334519 - Other Measuring and Controlling Device Manufacturing
SIC 3824 - Fluid Meters And Counting Devices
Sales $14,000,000
# of Employees 65
Plant Area (Sq.Ft.) 127,755
Annual Production 4,500 Pieces
Production Hrs. Annual 2,250
Location (State) SC
Source Yearly Cost Usage
Electricity Usage $64,398 1,335,000
Electricity Demand $72,930 5,772
Electricity Fees $1,602 -
Natural Gas $12,030 1,760,100
TOTAL ENERGY COSTS $156,339
RECOMMENDED SAVINGS* $20,835 *Non-energy impacts
included in savings.
IMPLEMENTED SAVINGS* -
#|Description Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW/month
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$4,261
Cost:
$1,269
$1,713 35,700 $2,548 201 $1,713
35,700
kWh
$2,548
201
kW/month
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$918
Cost:
$2,080
$369 7,693 $549 43 $369
7,693
kWh
$549
43
kW/month
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$5,441
Cost:
-
$2,188 45,581 $3,253 257 $2,188
45,581
kWh
$3,253
257
kW/month
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$2,586
Cost:
$1,600
$1,076 22,410 $1,511 120 $1,076
22,410
kWh
$1,511
120
kW/month
05: 2.7444 CLOSE HOLES AND OPENINGS IN BUILDING SUCH AS BROKEN WINDOWS Savings:
$139
Cost:
$900
$139 2,903 - - $139
2,903
kWh
-
-
kW/month
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$7,489
Cost:
$13,085
$3,224 67,164 $4,265 337 $3,224
67,164
kWh
$4,265
337
kW/month
TOTAL RECOMMENDED Savings:
$20,835
Cost:
$18,934
$8,709 181,451 $12,126 959 $8,709
181,451
kWh
$12,126
959
kW/month
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW/month
$ kWh $ kW/month
Electricity Usage Electricity Demand Electricity Usage Electricity Demand
Back to Top