Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Colorado School of Mines |
---|---|
Assessment Year | 2022 |
Principal Product | Educational Services |
NAICS | 611210 - Junior Colleges |
SIC | 8222 - Junior Colleges |
Sales | $1,000,000-$5,000,000 |
# of Employees | 424 |
Plant Area (Sq.Ft.) | 100,000 |
Annual Production | 2,000 Units |
Production Hrs. Annual | 8,760 |
Location (State) | CO |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $220,982 | 5,181,696 | kWh | $0.04 |
Electricity Demand | $171,386 | 9,558 | kW-months/year | $17.93 |
Electricity Fees | $4,152 | - | $ | - |
Natural Gas | $102,780 | 16,800 | MMBtu | $6.12 |
TOTAL ENERGY COSTS | $499,300 | |||
RECOMMENDED SAVINGS* | $73,233 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $33,003 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $12,003 Cost: $44,000 |
$6,729 | 160,300 | $5,274 | 380 | - | - |
$6,729 160,300 kWh |
$5,274 380 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7493 USE DOUBLE OR TRIPLE GLAZED WINDOWS TO MAINTAIN HIGHER RELATIVE HUMIDITY AND TO REDUCE HEAT LOSSES |
Savings: $1,800 Cost: $100,000 |
$600 | 15,800 | $700 | 39 | $500 | 64 |
$600 15,800 kWh |
$700 39 kW-months/year |
$500 64 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $410 Cost: $4,100 |
$240 | 5,500 | $170 | 7 | - | - |
$240 5,500 kWh |
$170 7 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.1133 ADJUST BURNERS FOR EFFICIENT OPERATION |
Savings: $4,300 Cost: $3,000 |
- | - | - | - | $4,300 | 530 |
- - kWh |
- - kW-months/year |
$4,300 530 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7314 REDUCE VENTILATION AIR |
Savings: $21,000 Cost: $740,000 |
$9,000 | 324,000 | $12,000 | 612 | - | - |
$9,000 324,000 kWh |
$12,000 612 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $32,600 Cost: $850,000 |
$32,600 | 358,000 | - | - | - | - |
$32,600 358,000 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $220 Cost: $860 |
$220 | 6,800 | - | - | - | - |
$220 6,800 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $900 Cost: $1,200 |
$500 | 14,000 | $400 | 33 | - | - |
$500 14,000 kWh |
$400 33 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $73,233 Cost: $1,743,160 |
$49,889 | 884,400 | $18,544 | 1,071 | $4,800 | 594 | $49,889 884,400 kWh |
$18,544 1,071 kW-months/year |
$4,800 594 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $33,003 Cost: $784,000 |
$15,729 | 484,300 | $17,274 | 992 | - | - | $15,729 484,300 kWh |
$17,274 992 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |