Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Colorado State University
Assessment Year 2007
Principal Product Printed circuit boards
NAICS 334412 - Bare Printed Circuit Board Manufacturing
SIC 3672 - Printed Circuit Boards
Sales $10,000,000-$50,000,000
# of Employees 80
Plant Area (Sq.Ft.) 40,776
Annual Production 1,300,000 Pieces
Production Hrs. Annual 4,862
Location (State) CO
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $77,765 1,927,997 kWh $0.04
Electricity Demand $101,380 7,003 kW-months/year $14.48
Electricity Fees $1,946 - $ -
Natural Gas $23,098 2,029 MMBtu $11.38
TOTAL ENERGY COSTS $204,189
RECOMMENDED SAVINGS* $15,100 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $2,450
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost
$ kWh $ kW-months/year $ $ $ $
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR Savings:
$4,720
Cost:
$19,200
$2,380 73,300 $2,340 164 - - - - $2,380
73,300
kWh
$2,340
164
kW-months/year
-
-
$
-
-
$
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,820
Cost:
$140
$990 30,400 $830 58 - - - - $990
30,400
kWh
$830
58
kW-months/year
-
-
$
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,860
Cost:
$10,220
$1,760 54,300 $1,660 116 $50 - $390 - $1,760
54,300
kWh
$1,660
116
kW-months/year
$50
-
$
$390
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,620
Cost:
$6,660
$1,310 40,200 $1,470 103 $10 - $(-170) - $1,310
40,200
kWh
$1,470
103
kW-months/year
$10
-
$
$(-170)
-
$
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$1,360
Cost:
$11,000
$470 14,600 $890 62 - - - - $470
14,600
kWh
$890
62
kW-months/year
-
-
$
-
-
$
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$630
Cost:
$850
$100 3,000 $60 4 $100 - $370 - $100
3,000
kWh
$60
4
kW-months/year
$100
-
$
$370
-
$
07: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$90
Cost:
$390
$80 2,500 $10 1 - - - - $80
2,500
kWh
$10
1
kW-months/year
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$15,100
Cost:
$48,460
$7,090 218,300 $7,260 508 $160 - $590 - $7,090
218,300
kWh
$7,260
508
kW-months/year
$160
-
$
$590
-
$
TOTAL IMPLEMENTED Savings:
$2,450
Cost:
$990
$1,090 33,400 $890 62 $100 - $370 - $1,090
33,400
kWh
$890
62
kW-months/year
$100
-
$
$370
-
$
Savings
Cost
$ kWh $ kW-months/year $ $ $ $
Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost