Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Colorado State University
Assessment Year 2011
Principal Product Wind turbine components
NAICS 335312 - Motor and Generator Manufacturing
SIC 3621 - Motors And Generators
Sales >$500,000,000
# of Employees 290
Plant Area (Sq.Ft.) 271,425
Annual Production 650 Pieces
Production Hrs. Annual 2,090
Location (State) CO
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $187,315 3,291,840 kWh $0.06
Electricity Demand $168,640 9,779 kW-months/year $17.25
Electricity Fees $1,220 - $ -
Natural Gas $39,043 5,691 MMBtu $6.86
TOTAL ENERGY COSTS $396,218
RECOMMENDED SAVINGS* $70,840 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$12,260
Cost:
$3,200
$12,260 248,400 - - - - $12,260
248,400
kWh
-
-
kW-months/year
-
-
MMBtu
02: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER Savings:
$9,530
Cost:
$20,000
- - $9,530 484 - - -
-
kWh
$9,530
484
kW-months/year
-
-
MMBtu
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$2,610
Cost:
$480
$2,610 52,800 - - - - $2,610
52,800
kWh
-
-
kW-months/year
-
-
MMBtu
04: 2.2711 UTILIZE OUTSIDE AIR INSTEAD OF CONDITIONED AIR FOR DRYING Savings:
$1,270
Cost:
$3,910
- - - - $1,270 178 -
-
kWh
-
-
kW-months/year
$1,270
178
MMBtu
05: 2.7145 INSTALL SKYLIGHTS Savings:
$38,050
Cost:
$70,550
$21,800 441,800 $13,890 705 $2,360 332 $21,800
441,800
kWh
$13,890
705
kW-months/year
$2,360
332
MMBtu
06: 2.7314 REDUCE VENTILATION AIR Savings:
$3,200
Cost:
$60
$330 6,600 $1,100 56 $1,770 249 $330
6,600
kWh
$1,100
56
kW-months/year
$1,770
249
MMBtu
07: 2.7264 INTERLOCK HEATING AND AIR CONDITIONING SYSTEMS TO PREVENT SIMULTANEOUS OPERATION Savings:
$2,770
Cost:
$60
- - - - $2,770 389 -
-
kWh
-
-
kW-months/year
$2,770
389
MMBtu
08: 2.7264 INTERLOCK HEATING AND AIR CONDITIONING SYSTEMS TO PREVENT SIMULTANEOUS OPERATION Savings:
$1,150
Cost:
$60
$120 2,500 $610 31 $420 59 $120
2,500
kWh
$610
31
kW-months/year
$420
59
MMBtu
TOTAL RECOMMENDED Savings:
$70,840
Cost:
$98,320
$37,120 752,100 $25,130 1,276 $8,590 1,207 $37,120
752,100
kWh
$25,130
1,276
kW-months/year
$8,590
1,207
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas