Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center South Dakota State
Assessment Year 1996
Principal Product Heat Conductive Material & Circuit Board Plates
NAICS n/a
SIC 3679 - Electronic Components, Nec
Sales $10,000,000-$50,000,000
# of Employees 140
Plant Area (Sq.Ft.) 55,000
Annual Production 563,200 Pieces
Production Hrs. Annual 7,488
Location (State) MN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $101,606 3,278,429 kWh $0.03
Electricity Demand $65,971 10,325 kW-months/year $6.39
Electricity Fees $5,730 - $ -
Natural Gas $199,893 90,663 MMBtu $2.20
LPG $7,500 1,380 MMBtu $5.43
TOTAL ENERGY COSTS $473,649
RECOMMENDED SAVINGS* $66,868 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $66,868
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)
$ kWh $ kW-months/year $ MMBtu $ lb
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$3,012
Cost:
$6,282
$1,848 59,496 $1,164 156 - - - - $1,848
59,496
kWh
$1,164
156
kW-months/year
-
-
MMBtu
-
-
lb
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$5,752
Cost:
$14,574
$3,578 115,475 $2,174 288 - - - - $3,578
115,475
kWh
$2,174
288
kW-months/year
-
-
MMBtu
-
-
lb
03: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$483
Cost:
$1,200
$483 15,533 - - - - - - $483
15,533
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
lb
04: 2.4224 UPGRADE CONTROLS ON COMPRESSORS Savings:
$629
Cost:
$20
$288 7,327 - - $341 153 - - $288
7,327
kWh
-
-
kW-months/year
$341
153
MMBtu
-
-
lb
05: 2.2443 RE-USE OR RECYCLE HOT OR COLD PROCESS EXHAUST AIR Savings:
$25,792
Cost:
$80,000
$(-3,615) (-81,477) - - $29,407 13,246 - - $(-3,615)
(-81,477)
kWh
-
-
kW-months/year
$29,407
13,246
MMBtu
-
-
lb
06: 3.1175 USE A DIFFERENT OR RECYCLED RAW MATERIAL Savings:
$31,200
Cost:
-
- - - - - - $31,200 168,000 -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$31,200
168,000
lb
TOTAL RECOMMENDED Savings:
$66,868
Cost:
$102,076
$2,582 116,354 $3,338 444 $29,748 13,399 $31,200 168,000 $2,582
116,354
kWh
$3,338
444
kW-months/year
$29,748
13,399
MMBtu
$31,200
168,000
lb
TOTAL IMPLEMENTED Savings:
$66,868
Cost:
$102,076
$2,582 116,354 $3,338 444 $29,748 13,399 $31,200 168,000 $2,582
116,354
kWh
$3,338
444
kW-months/year
$29,748
13,399
MMBtu
$31,200
168,000
lb
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ lb
Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)