Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Georgia Institute of Technology |
---|---|
Assessment Year | 2003 |
Principal Product | CARBONATED DRINKS |
NAICS | 312111 - Soft Drink Manufacturing |
SIC | 2086 - Bottled And Canned Soft Drinks |
Sales | $100,000,000-$500,000,000 |
# of Employees | 302 |
Plant Area (Sq.Ft.) | 404,211 |
Annual Production | 49,484 Tons |
Production Hrs. Annual | 4,080 |
Location (State) | GA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $594,704 | 12,579,650 | kWh | $0.05 |
Natural Gas | $452,000 | 106,251 | MMBtu | $4.25 |
TOTAL ENERGY COSTS | $1,046,704 | |||
RECOMMENDED SAVINGS* | $80,661 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,743 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Fees | Natural Gas | Water Consumption | Electricity Usage | Electricity Fees | Natural Gas | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | $ | $ | MMBtu | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1231 ESTABLISH BURNER MAINTENANCE SCHEDULE FOR BOILERS |
Savings: $5,393 Cost: $1,350 |
- | - | - | - | $5,393 | 1,269 | - | - |
- - kWh |
- - $ |
$5,393 1,269 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $226 Cost: $400 |
$214 | 7,571 | $12 | - | - | - | - | - |
$214 7,571 kWh |
$12 - $ |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1111 CONTROL PRESSURE ON STEAMER OPERATIONS |
Savings: $1,680 Cost: - |
- | - | - | - | $1,680 | 395 | - | - |
- - kWh |
- - $ |
$1,680 395 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $6,298 Cost: - |
$5,942 | 210,700 | $356 | - | - | - | - | - |
$5,942 210,700 kWh |
$356 - $ |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $1,058 Cost: $372 |
- | - | - | - | $1,058 | 249 | - | - |
- - kWh |
- - $ |
$1,058 249 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2121 INCREASE AMOUNT OF CONDENSATE RETURNED |
Savings: $17,688 Cost: $5,200 |
- | - | - | - | $17,200 | 4,047 | $488 | - |
- - kWh |
- - $ |
$17,200 4,047 MMBtu |
$488 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $35,980 Cost: $15,000 |
- | - | - | - | $35,980 | 8,560 | - | - |
- - kWh |
- - $ |
$35,980 8,560 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2621 MODIFY REFRIGERATION SYSTEM TO OPERATE AT A LOWER PRESSURE |
Savings: $9,570 Cost: $27,000 |
$9,570 | 301,090 | - | - | - | - | - | - |
$9,570 301,090 kWh |
- - $ |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $2,768 Cost: $14,000 |
$2,612 | 92,611 | $156 | - | - | - | - | - |
$2,612 92,611 kWh |
$156 - $ |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $80,661 Cost: $63,322 |
$18,338 | 611,972 | $524 | - | $61,311 | 14,520 | $488 | - | $18,338 611,972 kWh |
$524 - $ |
$61,311 14,520 MMBtu |
$488 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,743 Cost: $16,122 |
$8,768 | 310,882 | $524 | - | $6,451 | 1,518 | - | - | $8,768 310,882 kWh |
$524 - $ |
$6,451 1,518 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | $ | $ | MMBtu | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Fees | Natural Gas | Water Consumption | Electricity Usage | Electricity Fees | Natural Gas | Water Consumption |