Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Georgia Institute of Technology |
---|---|
Assessment Year | 2004 |
Principal Product | Door Mats |
NAICS | 314110 - Carpet and Rug Mills |
SIC | 2273 - Carpets And Rugs |
Sales | $10,000,000-$50,000,000 |
# of Employees | 61 |
Plant Area (Sq.Ft.) | 88,075 |
Annual Production | 11,057 Thousand Feet |
Production Hrs. Annual | 4,650 |
Location (State) | SC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $45,602 | 1,753,920 | kWh | $0.03 |
Electricity Demand | $71,699 | 4,922 | kW-months/year | $14.57 |
Electricity Fees | $16,307 | - | $ | - |
Natural Gas | $91,886 | 13,052 | MMBtu | $7.04 |
TOTAL ENERGY COSTS | $225,494 | |||
RECOMMENDED SAVINGS* | $29,962 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,781 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8112 COMBINE UTILITY METERS |
Savings: $4,508 Cost: $9,000 |
- | - | - | - | - | - | $4,508 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$4,508 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $895 Cost: $200 |
$373 | 14,334 | $522 | 47 | - | - | - | - |
$373 14,334 kWh |
$522 47 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $835 Cost: - |
$152 | 5,838 | - | - | $683 | 97 | - | - |
$152 5,838 kWh |
- - kW-months/year |
$683 97 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $815 Cost: $500 |
$548 | 21,110 | - | - | $267 | 38 | - | - |
$548 21,110 kWh |
- - kW-months/year |
$267 38 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1113 REDUCE COMBUSTION AIR FLOW TO OPTIMUM |
Savings: $8,427 Cost: $1,750 |
- | - | - | - | $8,427 | 1,197 | - | - |
- - kWh |
- - kW-months/year |
$8,427 1,197 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $5,639 Cost: $9,925 |
$2,823 | 108,610 | $2,816 | 350 | - | - | - | - |
$2,823 108,610 kWh |
$2,816 350 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,051 Cost: $50,551 |
$3,781 | 145,406 | $4,270 | 375 | - | - | - | - |
$3,781 145,406 kWh |
$4,270 375 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7313 RECYCLE AIR FOR HEATING, VENTILATION AND AIR CONDITIONING |
Savings: $792 Cost: $1,910 |
- | - | - | - | $792 | 112 | - | - |
- - kWh |
- - kW-months/year |
$792 112 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $29,962 Cost: $73,836 |
$7,677 | 295,298 | $7,608 | 772 | $10,169 | 1,444 | $4,508 | - | $7,677 295,298 kWh |
$7,608 772 kW-months/year |
$10,169 1,444 MMBtu |
$4,508 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,781 Cost: $50,751 |
$4,306 | 165,578 | $4,792 | 422 | $683 | 97 | - | - | $4,306 165,578 kWh |
$4,792 422 kW-months/year |
$683 97 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |