Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Iowa State University |
---|---|
Assessment Year | 2002 |
Principal Product | injection and blow molded plastic parts |
NAICS | n/a |
SIC | 3080 - |
Sales | $5,000,000-$10,000,000 |
# of Employees | 95 |
Plant Area (Sq.Ft.) | 70,000 |
Annual Production | 3,900,000 Pounds |
Production Hrs. Annual | 6,240 |
Location (State) | MN |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $183,093 | 5,125,598 | kWh | $0.04 |
Electricity Demand | $86,539 | 12,552 | kW-months/year | $6.89 |
Natural Gas | $16,124 | 3,029 | MMBtu | $5.32 |
TOTAL ENERGY COSTS | $285,756 | |||
RECOMMENDED SAVINGS* | $34,727 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $16,620 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,148 Cost: $409 |
$1,604 | 44,928 | $544 | 86 | - | - | - | - |
$1,604 44,928 kWh |
$544 86 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $418 Cost: $25 |
$312 | 8,736 | $106 | 17 | - | - | - | - |
$312 8,736 kWh |
$106 17 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,472 Cost: $253 |
$1,107 | 30,937 | $365 | 60 | - | - | - | - |
$1,107 30,937 kWh |
$365 60 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $4,148 Cost: - |
$3,099 | 86,796 | $1,049 | 167 | - | - | - | - |
$3,099 86,796 kWh |
$1,049 167 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,479 Cost: - |
$1,094 | 30,654 | $385 | 61 | - | - | - | - |
$1,094 30,654 kWh |
$385 61 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $686 Cost: $1,131 |
$686 | 19,220 | - | - | - | - | - | - |
$686 19,220 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,705 Cost: $7,590 |
$1,814 | 50,813 | $891 | 142 | - | - | - | - |
$1,814 50,813 kWh |
$891 142 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $1,520 Cost: - |
$714 | 19,993 | $806 | 128 | - | - | - | - |
$714 19,993 kWh |
$806 128 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.322 ELIMINATE OLD STOCK AND MODIFY INVENTORY CONTROL |
Savings: $13,000 Cost: $17,850 |
- | - | - | - | $13,000 | - | - | - |
- - kWh |
- - kW-months/year |
$13,000 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.5315 LEASE / PURCHASE BALER; SELL CARDBOARD TO RECYCLER |
Savings: $4,038 Cost: $10,900 |
- | - | - | - | - | - | $4,038 | - |
- - kWh |
- - kW-months/year |
- - $ |
$4,038 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS |
Savings: $3,113 Cost: $3,750 |
- | - | - | - | - | - | $3,113 | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,113 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $34,727 Cost: $41,908 |
$10,430 | 292,077 | $4,146 | 661 | $13,000 | - | $7,151 | - | $10,430 292,077 kWh |
$4,146 661 kW-months/year |
$13,000 - $ |
$7,151 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $16,620 Cost: $18,512 |
$2,711 | 75,865 | $909 | 146 | $13,000 | - | - | - | $2,711 75,865 kWh |
$909 146 kW-months/year |
$13,000 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||